The starters where i work dont seem to protect against phase loss. A year ago the whole place dropped a leg due to a defective recloser and took both hot and chilled water pumps with it.
I've had fused connected motor starters blow a single fuse single phasing the motor causing damage to the motor where as if the breaker was allowed to trip it would open all 3 phases not killing the motor.
I don’t suppose you have a video on setting up those sensors? I was always under the impression you needed special software and a laptop but it sure appeared as if you can do it without all that.
On older CH530’s I do use Trane software to bind sensors, these RTHD chillers can bind through the touchscreen with a PIN. I have an earlier video where I use the software on a CGAM. Thanks for asking Here’s a link : TRANE Chiller CGAM100 Water Temps High… Here’s What I Found #hvac #chiller #airconditioning ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-IXq7v1xCpqA.html