30hp condenser motor and pump reinstalled for our York YMC2 chillers and now Chiller 1 is starting to surge… #hvac #york #chiller #controller

Хобби

Опубликовано:

 

10 май 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 25   
@jasonjohnsonHVAC
@jasonjohnsonHVAC 2 месяца назад
Lot to unpack with that one. That'll keep a guy busy for a little while. Good stuff broham.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
This is a fun one, we’ll get it figured out. Thanks Jason 👊
@BOBKB3NZX
@BOBKB3NZX 2 месяца назад
It's wild what you find from a system that was otherwise "running fine" one leg gets wobbly and then you uncover the house of cards
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Yep, problems have a way of presenting themselves. 😎
@ericbaker5619
@ericbaker5619 2 месяца назад
Thanks for the video! Seems like we are going to see more of these Dork chillers. I'm not a fan of JCI
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Lol, these replaced York R22 and R11 open drives.
@thesilentonevictor
@thesilentonevictor 2 месяца назад
Good find experience pays off
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks SilentoneVictor 👍
@trailerparkguns
@trailerparkguns 2 месяца назад
found your channel i love it. at a risk of sounding dumb is this a small part to a massive air conditioning system my local hospital has a massive set of evapco towers on a two story standalone building always wondered what it was for
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks for asking, yes these are the cooling towers for a couple of Centrifugal chillers (200 & 300 Ton) that cool many commercial buildings
@HEFTYLEFTY303
@HEFTYLEFTY303 2 месяца назад
York ymc2 like to see as cold of condenser water as you can get 55 or 60 degrees but you are in florida
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Entering CWT was set 85 , I know Yorks are able to run colder CWT
@HEFTYLEFTY303
@HEFTYLEFTY303 2 месяца назад
I would of liked to see where condenser liquid level setpoint was at
@subcoolHVAC
@subcoolHVAC 2 месяца назад
It was set at 38% not sure why, ran out of time troubleshooting… returning soon
@jasonjohnsonHVAC
@jasonjohnsonHVAC 2 месяца назад
@subcoolHVAC we have some YK's we had to adjust to 42% to get them to run right and not loose the liquid seal
@subcoolHVAC
@subcoolHVAC 2 месяца назад
I think 42% will do it. My access level wouldn’t allow me to change it. York and their Access Manager control 👎
@jasonjohnsonHVAC
@jasonjohnsonHVAC 2 месяца назад
@@subcoolHVAC I hat that access manager crap. I have the passwords for the ones they don't have their meathooks sunk into
@zekenzy6486
@zekenzy6486 2 месяца назад
Great Video. Thank you for sharing. Have a nice weekend. May I ask, Which's Refrigerant this chiller is using R22 or R410 A ? and second is: There are 2 sight glass , is those sight glass show refrigerant or water ?
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks, it’s R134a refrigerant. That is refrigerant seen in the sight glass.
@jratti2006
@jratti2006 2 месяца назад
My good sir. What flashlight is that? And how’s the battery life?
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Blackfire BBM6412 , rechargeable battery has good life, 2 levels of brightness is spotlight or lantern mode. Magnet is strong 💪
@colossalsky
@colossalsky 2 месяца назад
Are these pumps for cold storage industrial buildings?
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Condenser pumps for 2 York Centrifugal chillers used for Air Conditioning
@colossalsky
@colossalsky 2 месяца назад
@@subcoolHVAC oh cool it’s interesting too see the different types of air conditioners, I work in a cold storage facility that’s cool the freezer with anhydrous ammonia that stuff is crazy scary
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Never worked with Ammonia systems, toured a plant during apprenticeship many years ago. Impressive 👍
Далее
Water cooled AAON
6:49
Просмотров 2,2 тыс.
York YMC2 Service Needed || That Doesn’t Sound Good
7:03
Advantage glycol chiller  service call
26:13
Просмотров 10 тыс.
THE SMOKE IS ROLLING OUT OF THE HOOD
19:37
Просмотров 29 тыс.
YK Overview Centrifugal Chiller York HVAC Training
27:47
The Most Confusing Part of the Power Grid
22:07
Просмотров 1,4 млн
Наше обычное утро 💕
0:42
Просмотров 2,1 млн
гороховый СУП
0:57
Просмотров 1,6 млн
越野卡丁车WhatsApp  +86 19133971897
0:17
Просмотров 6 млн