TRANE RTHD’s Had Trouble Restarting After Power Outage | EMS Override! 

Subcool HVAC
Подписаться 4,5 тыс.
Просмотров 8 тыс.
50% 1

Got a work order stating chillers not starting up , had to troubleshoot where the night crew left off #chiller #hvac #airconditioning

Хобби

Опубликовано:

 

11 апр 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 38   
@djcode4714
@djcode4714 2 месяца назад
Tom. glad you understand what you do very well. Getter done!😊
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks 👍
@LESWEGENER
@LESWEGENER 2 месяца назад
For your noise in the tower gearbox, many times the drive will set up harmonics in pumps and fans that cause noise. One B&G pump rep called it "cogging". Most drives will let you skip over frequency areas that cause issues. So just play with drive in manual control and record the troublesome frequency's and exclude the drive from operating in these areas. Good job figuring out what happened and following trail of the illusive "maintenance man/ service work creator". I used deal with a building that had the cooling basin was the lowest point in the system, one power blink and a large percentage of the tower water was on the ground and the tower pumps were trying to pump air. Enjoy you time at the service trade!
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Excellent, Thanks for that tip, it seemed to be more noticeable in the mid 20HZ - 30HZ range . Makes sense 👍
@TheChillerGuys
@TheChillerGuys 2 месяца назад
good stuff brother, hopefully things have been going good!
@subcoolHVAC
@subcoolHVAC 2 месяца назад
All is good 👍
@anthonyc826
@anthonyc826 2 месяца назад
I appreciate your content man. We work on similar equipment and when I’m scheduled for a service call I use your videos as reference tysm
@subcoolHVAC
@subcoolHVAC 2 месяца назад
I’m glad it’s helpful, Thanks for sharing 👍
@ericbaker5619
@ericbaker5619 2 месяца назад
The shaft on that motor on tower 1 looked a bit wobbly. Thanks for the video bud
@subcoolHVAC
@subcoolHVAC 2 месяца назад
I think it’s the shaft key and anti-seize making it look that way, I was wobbling too up there! Thanks Eric !
@thesilentonevictor
@thesilentonevictor 2 месяца назад
Good troubleshooting
@subcoolHVAC
@subcoolHVAC 2 месяца назад
👍 Thanks!
@fortniteinminecraftt3794
@fortniteinminecraftt3794 2 месяца назад
0:16 are we inside the matrix
@subcoolHVAC
@subcoolHVAC 2 месяца назад
😎 💯 Real
@stevencossaboon3237
@stevencossaboon3237 2 месяца назад
Nice work Subcool.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks Steven 👍
@NROhvac
@NROhvac 2 месяца назад
Good work subcool
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks Nick 👍
@nickcemelli6255
@nickcemelli6255 2 месяца назад
there is a simple solution of putting a reverse trap on the end of that line to keep it full of water and not overflowing your tower or draining your sump when the pump starts up
@subcoolHVAC
@subcoolHVAC 2 месяца назад
There may be a check valve sticking the more I thought about it. Thanks for the suggestion too 👍
@ccthepope
@ccthepope 2 месяца назад
nice video!
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks for watching cc 👍
@zekenzy6486
@zekenzy6486 2 месяца назад
Great Video. Thank you for sharing. Have a nice weekend. Why is cooling Tower have alot water like pool ?
@subcoolHVAC
@subcoolHVAC 2 месяца назад
The Basin collects the cooled condenser water being circulated through the condenser loop, the pump draws from the bottom of Basin 100% liquid to avoid air cavitation . Thanks for the question 👍
@syedbasheer2299
@syedbasheer2299 2 месяца назад
✅👍👍👍
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks for watching!
@Mr89netrom
@Mr89netrom 2 месяца назад
Sounds like the gearbox is crapped out? Or a bearing in there going bad. Perhaps it has been low on oil before, and there is a missaligment of the gears?
@seangriffon6502
@seangriffon6502 2 месяца назад
Great video. What do yo think of those ABB variable frequency drives? Reason i ask is because i work on a chiller at an ice rink as well as a big high school, and they both have those same drives, but they have been very problematic. More so the ones at the high school than the ice rink. The school chiller is a carrier unit and the cooling tower is a BAC Baltimore Air Coil brand. I have also worked on the Evapcos as well. What i like about the BAC cooling tower is the fan motors are right inside the tower, and use a belt and pully to turn the blade which i think is way better than that drive shaft system that evapco uses like the one here in this video. Now dont get me wrong, changing those bearings on the bac towers can be a pain especially if the bolts are rusty. I have did many. The ice rink chiller is made by Cimco Toromont, and uses R 717 Amoina for the refrigerent, and glycol for the secondary coolant that is chilled and pump through the tubing in the rink floor. These chillers can be a pain. Also they are not that good at removing the humidity like a standard ac unit will do. You have to have a stand alone dehumidification system with a chiller. The ice rink has a Munters brand dehumidifaction unit. Lots to these systems. Takes people with good knowledge and dedication to keep them maintained.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
We mainly use ABB drives with good results with the correct motor info setup
@georgebrabec1749
@georgebrabec1749 2 месяца назад
Great job are you looking at R/R the gear box or the motor ?
@subcoolHVAC
@subcoolHVAC 2 месяца назад
If anything would be gearbox. Thanks
@paulpipitone8357
@paulpipitone8357 2 месяца назад
If you don’t mind what kind of watch are you wearing
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Sure, apple watch 8 series 45mm with amband strap. Thanks for watching! Apple Watch Series 8 [GPS 45mm]... www.amazon.com/dp/B0BDJDH2WR?ref=ppx_pop_mob_ap_share
@davidnull5590
@davidnull5590 2 месяца назад
There are T-shirts available with "I'm not to be truffled with" "Michael says the phrase when he sets rules and people follow them blindly. He also says, "No matter how I look at this, I am in the wrong. And I have looked at this thing like 100 different ways, from my point of view, from their point of view, 98 others, and bottom line: I am in the wrong. I'm the bad guy"."
@subcoolHVAC
@subcoolHVAC 2 месяца назад
I would never Truffle my Boss 🤣 Thanks for the compliment 👊👍
Далее
Zlatan embarrasses Speed 😂 #ishowspeed
00:32
Просмотров 8 млн
She called the Fire Department after I left
17:55
Просмотров 456 тыс.
My new building as a building engineer !
20:58
Trane RTAC Leak Repair + Oil Filter Part 1
19:57
Просмотров 11 тыс.
Carrier RTU Start-Up From Hell
34:43
Просмотров 14 тыс.
тг: @keyneceee  #корея #корейцы
1:01
Просмотров 2,7 млн
A day of battle of wits between a dog and his owner
0:37