York Ymc2 Chillers Shutdown Shortly After Scheduled Start Time… Tripped Main.. No Display VFD 

Subcool HVAC
Подписаться 4,5 тыс.
Просмотров 16 тыс.
50% 1

Was contacted early in the morning prior to shift start by a coworker that the chillers abruptly stopped after starting, no pumps or chillers running, no display on vfd’s and a main breaker tripped…Priority work order generated and Here’s how we responded #chiller #york #hvac

Хобби

Опубликовано:

 

21 апр 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 60   
@ericbaker5619
@ericbaker5619 2 месяца назад
Crazy that motor didn't show short when you two tested at the disconnect at the motor. Thanks for the video.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
I know, I was expecting to find one grounded. Better the pump motor than a tower motor 🫡
@Byron88
@Byron88 2 месяца назад
It's surprisingly common, after it blows the arc usually breaks the short, but its so close to being grounded as soon as you apply voltage again it arcs again, as you saw after the megger showed 0Mohm at almost 0 volts, the fault would have showed up right away with a megger vs a standard ohmmeter
@craiglewis8272
@craiglewis8272 Месяц назад
@@Byron88yeah. That’s why I don’t like using a standard meter when checking for grounded motor
@ayoutubewatcher7009
@ayoutubewatcher7009 2 месяца назад
I miss working on the larger tonnage equipment, but not really.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
I hear you 👍 Thanks for watching!
@ShaunPuzon
@ShaunPuzon 2 месяца назад
Your editing work is on point, sir! Yet another great video!
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks Shaun 👊
@littleprincess4417
@littleprincess4417 2 месяца назад
We once had a wire on a 277 volt 20 amp lighting circuit bypass not only the 20 amp breaker, but also the 225 amp breaker in the distribution panel and go back and get a 800 amp breaker in the MDP.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
That’s a strong willed wire 😃 Thanks for sharing
@mxslick50
@mxslick50 2 месяца назад
You should probably replace the contacts in that starter, closing into a short (and it opening on the original fault) would have pitted the contacts pretty bad. At the least, do a voltage drop measurement across all three contacts when you get the new motor running. Any voltage greater than about 2v across those contacts means they are bad.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Definitely 👍
@dgapp76
@dgapp76 2 месяца назад
Agreed
@SupraTompan
@SupraTompan 2 месяца назад
You simply measure voltage before and after contacts? I would not have thought about this.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Measure volt across contacts while energized, Thermal camera will also help determine if excessive heat is being generated in any contacts. 0 drop is 👍
@dgapp76
@dgapp76 2 месяца назад
I was told by an old AC duffer years ago to make sure you keep the smoke in. 😅
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Yep, I heard that too 😃
@TheChillerGuys
@TheChillerGuys 2 месяца назад
It’s so hard to put it back in after you let it out too… 😅
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Expensive too
@jasonjohnsonHVAC
@jasonjohnsonHVAC 2 месяца назад
Yeah buddy....she gave up the ghost in style. Let the magic smike out....kinda lost opportunity for your helper to have gathered it back up in a bucket...😂😂😂😂....that smoke is valuable.....im just playing around. Great video as always
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Oh yeah, nothing like some bbq first thing in the morning. At least the apprentice got to see his first motor smoke release 😁Thanks Jason 👍
@plushdragon
@plushdragon 2 месяца назад
where someone with a paper bag to go boom when you reset the mains
@subcoolHVAC
@subcoolHVAC 2 месяца назад
😃
@LilyRoseElectric
@LilyRoseElectric 2 месяца назад
Great job 👏
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks 👍
@JW-qp5uf
@JW-qp5uf 2 месяца назад
Why are the chillers run in series? Are the temps higher on chiller 1 going into 2? Thanks for the video.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
There’s only 1 chilled water pump on this chiller plant, yes chiller 1 receives the warmer return water from the loop then passes through chiller 2 . Thanks for the question 👍
@djcode4714
@djcode4714 2 месяца назад
yay. another one bites them dust!
@subcoolHVAC
@subcoolHVAC 2 месяца назад
😎
@TheChillerGuys
@TheChillerGuys 2 месяца назад
Awesome stuff man!
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Appreciate it!
@guygfm4243
@guygfm4243 2 месяца назад
Thanks for sharing
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks for watching!
@MariMuthu-ck5ih
@MariMuthu-ck5ih 2 месяца назад
Good job 👍👍
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks 👍
@fellpower
@fellpower 2 месяца назад
For a fast check, u can measure the resistance of the motors, but if u want to make it right, u should measure with an insulation tester, because it can be moisture on a broken cable / motor or something like that. with an insulation tester - u can find that
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks for Watching!
@stevencossaboon3237
@stevencossaboon3237 2 месяца назад
Nice work Subcool.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks!
@BOBKB3NZX
@BOBKB3NZX 2 месяца назад
I've noticed on higher current application that breakers meant to trip before a main will get stuck and not trip when they're supposed to. Maybe a quarterly exercise of them may alleviate that
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks for the suggestion 👍
@ickipoo
@ickipoo 2 месяца назад
I think the issue is simply the peak fault current, which every breaker in series will see simultaneously. A sudden hard fault will have a high enough current to trip upstream breakers. In some applications, some series resistance or inductance is required to limit fault currents to manageable levels - breakers are only rated to break a certain fault current.
@mrfrenzy.
@mrfrenzy. 2 месяца назад
The main breaker should be programmed to prevent this, I would have a good electrician check the calculations and programming.
@zekenzy6486
@zekenzy6486 2 месяца назад
Great Video. Good Job and Nice Work. Thank you for sharing. Is that motor pump short to ground is that why's chillers was tripped Main breaker ? Please. Could we have part 2 replace motor pump ^_^
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Yes, motor shorted to ground. Thanks for the question. Part 2 is possible 👍
@rock7282
@rock7282 2 месяца назад
Time to go with a new generation Baldor motor
@subcoolHVAC
@subcoolHVAC 2 месяца назад
👍
@anthonybush3134
@anthonybush3134 2 месяца назад
What are you going to do with that impeller from the old pump?
@subcoolHVAC
@subcoolHVAC 2 месяца назад
The pump was removed to replace bearings and seals
@brent562
@brent562 2 месяца назад
How much a motor like that cost?
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Somewhere between $4k-$5k depending on availability , I don’t do the purchasing though. Thanks 👍
@lilpbass
@lilpbass 2 месяца назад
I got some magic smoke I can sell you 😂
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Sold 👍🤣
@user-ge5le4ku6j
@user-ge5le4ku6j 2 месяца назад
why no disconnect at the motor?
@subcoolHVAC
@subcoolHVAC 2 месяца назад
There are disconnects 👍
@mxslick50
@mxslick50 2 месяца назад
Try watching the whole video.....
@Cinncinnatus
@Cinncinnatus 2 месяца назад
if you check to ground you should first check from ground to ground to make sure you actually getting a proper probe contact. 3:45 Not saying something done totally wrong either just as you shown in the video earlier probe contact isnt always perfect so should be teaching them to get into the habit of making sure the ground is being read properly first.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
It’s more likely the initial short to ground cleared and when power applied it arced to ground again. Thanks for commenting
@Cinncinnatus
@Cinncinnatus 2 месяца назад
@@subcoolHVAC oh I wasn't referring to the cause nor am I implying it was overlooked/missed. Just saying you skip teaching a crucial step when checking for shorts to ground. Should always test first from ground to ground then test your lines/loads. If you just take your probe to a ground then use the other and start looking for shorts you assume to know that your grounded probe has proper contact.
@subcoolHVAC
@subcoolHVAC 2 месяца назад
Thanks for watching
Далее
Nurse's dream !! 😂😂
00:17
Просмотров 2,3 млн
Your church organ needs a huge infra-subwoofer.
6:26
Просмотров 113 тыс.
2 Bad Compressors In Weeks WHY? Freezer Down
29:40
Просмотров 15 тыс.
Crucial Knowledge To Heat Pump Troubleshooting
14:15
Просмотров 20 тыс.
Решил Проблему Из Детства 😍
0:33