This is the 2nd video in the economizer series and also the 1st of video specific to the JADE controller. This segment covers setup, advanced setup, and setpoints.

Наука

Опубликовано:

 

30 июл 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 32   
@saltrue1555
@saltrue1555 5 лет назад
Thank you very much for your teaching,I dint get the whole thing I’m slow learner but I will keep watching your videos,thank you and God bless you for your teaching.
@tomsipes5168
@tomsipes5168 4 года назад
Great videos. It made it much easier to learn because you showed how to make the changes live and what they meant. Than you!
@danpmatz
@danpmatz 2 года назад
Just wanted to tell you this is an awesome video you have made I just installed one of these and with your help it was short work
@COAC-jz2we
@COAC-jz2we 4 года назад
Fantastic video absolutely appreciated every second man
@l.crossjr
@l.crossjr 6 лет назад
Great instructor
@TECTubefilms
@TECTubefilms 6 лет назад
He's alright. ;)
@itsmemsti
@itsmemsti 5 лет назад
Thanks for this
@lancerudy9934
@lancerudy9934 5 лет назад
Very nice
@thisguyslifeboardgamenatio8492
Thank you for great work in this training!
@odeliocepeda6054
@odeliocepeda6054 3 года назад
Thank you so much . I appreciate the four version series for the economizer setup. I have a quick question how can I access the simulator on the computer so I can set up my economizer ?
@dand1486
@dand1486 2 года назад
great video! whats a common wb set point? i seen 65f, seems too high but maybe not?
@TECTubefilms
@TECTubefilms 2 года назад
You do not have the ability to set the wet bulb. If you have the enthalpy version of JADE, or any other economizer controller, you are picking a "curve." If you look at the curve for JADE, it is controlling to enthalpy setpoint straight line (with the top wet bulb chopped off and the far right dry bulb chopped off. The wet bulb will vary along those lines. It is hard to explain without looking at the curves on a psych chart. But even if you picked the most aggressive enthalpy setpoint (ES1), the highest point that it would ever get for wet bulb would be about 62. If you pick ES2, which we frequently recommend, it would be 59 WB at the highest.
@dand1486
@dand1486 2 года назад
@@TECTubefilms thx for the response. i can reference a psychometric chart, not to familiar with this controller as i do mainly refrigeration racks . im guessing es1, es2 etc is like a b c d on a conventional entalpy controller?
@TECTubefilms
@TECTubefilms 2 года назад
@@dand1486 Yes, the ES curves are sort of like the old ABCD curves, but they are a much different shape. They start horizontal on a dewpoint line, then follow a wet bulb line, then a dry bulb line. Instead of curve like ABCD with suspect situations at the far ends, these new ES curves essentially cut those ends off. We wish we could post pics in the RU-vid chat to show you what we mean.
@nickmiller4544
@nickmiller4544 6 лет назад
How many actuator I can connect to 2-10 vdc output terminal? I have 3 independent actuator for OA,RA,and exhaust air. Thanks
@TECTubefilms
@TECTubefilms 6 лет назад
Check out page 2 of the JADE installation manual. It can support 1 communicating actuator, but up to 4 non-communicating actuators.
@Slap_it_in
@Slap_it_in Год назад
Why does the DAMPER OUT show 9% when when set to 2.8V and not 10%
@juamondragon
@juamondragon 4 года назад
Hi iam installing 26 of this economizers and on my bp show automatic 24 v damper one for RA and one for Relief air. between the roof and the economizer What terminal I need to use connect the externals dampers ..
@TECTubefilms
@TECTubefilms 4 года назад
This economizer controller... and almost all RTU economizer controllers... have a single modulating output for the damper actuator(s). A motorized exhaust air damper needs to modulate the same direction as the outside air damper (the more you suck in the, the more you need to relieve). The return air damper needs to be wired to do the opposite of the outside and exhaust dampers. So one output can control all three dampers and you just need to switch the rotation (CW or CCW) at the actuators.
@markkozlowski6776
@markkozlowski6776 3 года назад
If you need a minimum damper position of 20% , if 10% is 2.8v , 100% is 10v what voltage would it for 20%
@TECTubefilms
@TECTubefilms 3 года назад
3.6v is 20% because it is 20% of the way between 2v and 10v. But a better question would be why do you need 20%. All building codes dictate an OA CFM, not an OA percentage. So do not set minimum code damper position based on %.
@markkozlowski6776
@markkozlowski6776 3 года назад
@@TECTubefilms it would be starting point to know how far to open the damper
@markkozlowski6776
@markkozlowski6776 3 года назад
@@TECTubefilms what would be your prefer method of measuring OA ?
@TECTubefilms
@TECTubefilms 3 года назад
@@markkozlowski6776 The damper minimum percentage should be set to provide the code minimum required CFM for that specific space
@TECTubefilms
@TECTubefilms 3 года назад
@@markkozlowski6776 We like to measure OA percentage and CFM using temperatures for OA, RA, and MA and doing a little math.
@TheGpaul
@TheGpaul Год назад
Too complicated most of the time I just just disconnect them my lack of understanding too complicated.
@TECTubefilms
@TECTubefilms Год назад
Or hope was that the training videos would make them a little less complicated for techs who feel the way you do.
@derekameduri4703
@derekameduri4703 5 лет назад
Allot to know. You are very informed, thank you for sharing. I have noticed that allot of these controllers and zone boards are not very user/service friendly. This should be an app on the phone where you (the service tech/contractor) can Bluetooth directly in. That way it has better descriptions than whats displayed on this little screen as well as the abbreviations that only make sense to the people who made the darn thing. I know my luck, I will be working on a economizer controller for a computer lab where the co2 sensors are notifying the principles iphone cause the economizer is stuck shut with 200 students in the lab. This would be on a day its raining cats and dogs with alarms and error codes going off and abbreviation that even tech support gets stumped on. Ill probably be curled up under the stuck shut economizer on my phone anyways looking for literature on this controller cause of course the manual is gone. Not trying to bash this beautiful peace of technology, but i would pay a significant amount more for this work of art to allow Bluetooth capability/programming and parameter setting . This goes for all of honeywells controllers and zone boards.
@TECTubefilms
@TECTubefilms 5 лет назад
After years of teaching controls classes to technicians, there is one thing we know for certain. The vast majority of mechanical techs do not want anything that has to connect to their phone. Honeywell learned this the hard-way with the first version of the Lyric Round. Techs hated trying to connect it to their phone. We also have Bluetooth connectivity to some of our hydronic pumps and the techs NEVER use it. Adding a Bluetooth chip to a high manufacturing volume product like this would increase the cost for everyone but only be used by a select few. We would rather they solved your concern with an upgraded display and larger processor so the screen on the device itself can give you "help buttons" that essentially include the manual.
@danpmatz
@danpmatz 2 года назад
Remote access would be nice Bluetooth is only a short distance you might as well go to the control
Далее
Economizer Trickery - Air Conditioning Troubleshooting
13:09
Я КУПИЛ САМЫЙ МОЩНЫЙ МОТОЦИКЛ!
59:15
Air Side Economizer
7:33
Просмотров 17 тыс.
Honeywell Economizer Fundamentals
14:07
Просмотров 1,5 тыс.
HVAC - Honeywell Jade Economizer
8:00
Просмотров 13 тыс.
JACE 8000 Start up
23:36
Просмотров 18 тыс.
Economiser X   Installation and Wiring 2
5:33
Просмотров 33 тыс.
Honeywell Jade Controller Status and Checkout Video
6:04
Servicing Existing RTU Economizer Controls
7:58
Просмотров 2,8 тыс.
Economizer Tech Tips
2:55
Просмотров 1,9 тыс.
ICP RTU Economizer & JADE Installation
9:57
Просмотров 8 тыс.
Новые iPhone 16 и 16 Pro Max
0:42
Просмотров 2,1 млн
ЗАБЫТЫЙ IPHONE 😳
0:31
Просмотров 20 тыс.
How to Soldering wire in Factory ?
0:10
Просмотров 6 млн
КРУТОЙ ТЕЛЕФОН
0:16
Просмотров 6 млн