Manual Paralleling and Synchronization of generators onboard Live demonstration of the process Explanation why the synchroscope needs to be switched of after use. Connect on allabout_marine
How do you regulate power factor of parallel running DG sets. I made a panel DG were synchronised both ACB closed but the power factor of one or both DG set was very low.
what happens if we arrange load sharing manual or auto while we are paralelling the generators? in the video load sharing is in auto mode, i am asking the reverse situation.
Manual load sharing is accomplished by adjusting the speed input to each generator’s governor. Once synchronized, the generator will no longer change in speed when this control is adjusted, but the output of the generator will vary with the setting. The power produced by each operating generator can be adjusted by their individual speed adjustment setting to shift load from one to another generator and to share load.