The following formula is used to convert analog values: Scaled value = (Input value * Rate) + offset Where: Rate = (Scaled max) / (Input max - Input min) Offset = Scaled min - (Input min * Rate) Meaning of individual variables: Scaled value - in physical units Input value - The current value at the analog card input Rate - The conversion constant Scaled max - Maximum value (in physical units eg 100bar) Scaled min - Minimum value (in physical units eg 0bar) Input max - Maximum unit on the analog card input (32767) Input min - Minimum unit on analog card input (0) Offset - Correction of recalculated value