Understanding Current Limit Fuses and let through current 

Jonathan Gracey
Подписаться 1,4 тыс.
Просмотров 41 тыс.
50% 1

Examples are provided explaining the fuse graphs of a current limiting fuse. First over current protection is discussed and the TCC fuse melt chart is examined with examples. Next we look at the current limitation curves to determine the symmetrical let through current and an example is provided. A class L fuse is used in the examples

Опубликовано:

 

7 апр 2018

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 38   
@sovidelectro8383
@sovidelectro8383 8 месяцев назад
Wow! Thanks bro, you save the day. You are the only guy who perfectly demonstrates how and why the value of minimum fusing current is greater than the rated current of the fuse! I can sleep well tonight, Cheers!
@sudh304kapoor
@sudh304kapoor 23 дня назад
Thanks for explaining this topic , nice explanation
@AudioJunkie79
@AudioJunkie79 5 лет назад
I love RU-vid. This made understanding these charts super easy. Thank you.
@jidetaiwo3830
@jidetaiwo3830 5 лет назад
Nice tutorial video, it has really broadened my knowledge of fuses and their current limiting characteristics. Thanks.
@SuperGurumoorthy
@SuperGurumoorthy 3 года назад
Great explanation, Thank you sir !
@Huzzeram
@Huzzeram 4 года назад
Gr8 explanation sir. Thanks
@lhmachado81
@lhmachado81 5 лет назад
Thanks man. Great vídeo tutorial
@sureshk6504
@sureshk6504 5 лет назад
Great .. explained..sir..tq
@sohailjanjua123
@sohailjanjua123 3 года назад
Hi, I like your lecture. Thanks
@ianrebello9008
@ianrebello9008 5 лет назад
fantastic. thanks
@user-ny5be4lm8z
@user-ny5be4lm8z 2 года назад
yes just what i needed
@akramal-frigy1143
@akramal-frigy1143 2 года назад
Thank you
@user-yd1mr6ir9d
@user-yd1mr6ir9d 8 месяцев назад
Love it
@AlesperEng
@AlesperEng 4 года назад
THANKS
@graceyj20
@graceyj20 4 года назад
Glad you found it helpful
@seaselol
@seaselol 3 года назад
Thanks Jonathan, i am only confused on your last sentence. Once the 800A fuse melt due to 100kA fault, shouldn't be the fault level is cleared? Assuming the Fuse in connected in series with the system, the fault will be isolated from the down stream isnt it?
@graceyj20
@graceyj20 3 года назад
Hi Zen, yes the fault will be isolated after approx 0.01 seconds. Prior to that it'll let through 22k in my example. It may not have been the best example as the time is so brief... as another imaginary example, let's say there was 25kA of fault current and that some current limiting fuse had a let through of 10KA and a trip at 0.3 seconds then you can see how the let through is more useful as the downstream device will have to withstand many cycles under a fault before the fuse will trip. Hope that helps!
@tuna6423
@tuna6423 Год назад
Hi Jonathan, Is my understanding correct that Let through limiting fuse is not required to blow its own to get characteristic of limiting current to downstream? Just current pass through it and it already limited current to downstream without blown itself?
@IEPBrasilia-Marco_Oliveira
@IEPBrasilia-Marco_Oliveira 5 месяцев назад
Hello, any recommendations for an application to calculate the NH Fuse Melting Time?
@shelfrobthomas449
@shelfrobthomas449 4 года назад
Nice tutorial, how about R-rated fuses does it follows the same concept
@graceyj20
@graceyj20 4 года назад
Glad you found it helpful. Yes, RK1 & RK5 fuses follow the same concept.
@azzamalgoraee2847
@azzamalgoraee2847 5 лет назад
In the first example, If the current dropped back to 800A before it gets 18 seconds, What would happen?
@graceyj20
@graceyj20 5 лет назад
If the current dropped to 800A before it tripped then nothing should happen at 18 seconds. The fuse should theoretically trip at 800A but over a longer period. As the trip is thermal (melt) the heating up at 3000A for say 17 seconds would be relevant with respect to the trip point if dropped to 800A. If it dropped to say 799 Amps at 17 seconds then it should never trip, in theory. Circuits are not supposed to be more then 80% loaded so a properly designed circuit with an 800A fuse shouldn't have more then 640A of constant draw.
@David_prod-eNGee
@David_prod-eNGee 3 года назад
UL 508A is concerned with Peak let-thru, not Symmetrical RMS, when determining the short-circuit current rating of an electrical enclosure.
@graceyj20
@graceyj20 3 года назад
Thanks for you comment. Certainly some standards so however NEC (2017) focuses on the symmetrical rating. See article 100 Definitions for Short Circuit Current Rating.
@zidanetribal2343
@zidanetribal2343 3 года назад
@@graceyj20 How to evaluate this? I have a scenario where using current limiting fuses would normally consider the symmetrical RMS even major fuse manufacturers will highlight the consideration of the sym. RMS not the peak let through. But say a client will want to require the consideration be in "peak let thru" and even highlight SB4.3.3 as a reference. so clearly this is a battle of consideration between the one with "peak" and those with "rms" please advise. I am so confuse right now.
@graceyj20
@graceyj20 3 года назад
@@zidanetribal2343 Typically NFPA 70 (NEC) requires all components to be rated for the symmetrical fault current they may be exposed to. There are exceptions though such as manufacturer approved series rated devices. Other standards have different requirements and methodologies. NRTL's such as UL also approve manufactured assemblies where the assembly provides an integrated designed unit that has undergone independent testing and has specific operational guidelines. Ultimately it comes down to the details of the circumstance, engineering judgement and what the authority having jurisdiction will permit. With respect to safety and liability, one can never go wrong with a fully rated unit.
@zidanetribal2343
@zidanetribal2343 3 года назад
@@graceyj20 I see, so it goes down on where and what a scenario will require like in all standards, if say company A will require compliance with standard X then by all means we will comply with standard X and also if company B will require adherence to standard Y then we should follow. Thank you so much.
@leofawkeyla2944
@leofawkeyla2944 2 года назад
i was downloading the catalog time-current characteristics of the nh fuse, but in the picture above the graph there is no description of the current rating. can you help me?
@graceyj20
@graceyj20 2 года назад
You should contact the manufacturer if their data sheet isn't properly marked.
@RizwanKhan_99
@RizwanKhan_99 4 года назад
But why let through the 20kA fault currenti in the first Place. wouldn't that just damage the downstream circuit
@graceyj20
@graceyj20 4 года назад
There's a few things to consider, first most standard overcurrent protection device have to let through more current than it's rated for for a brief time to handle inrush current (motor, transformer, etc). Past that, yes it's ideal not to let through any fault current I'm not aware of any mass market protective devices that does this. "Instant" trips always have a minor melt time, latching time, etc so during that time there will be some level of fault current. Some fuses and circuit breakers specialize in minimizing let through current. Past that, the downstream devices need to be rated to carry whatever potential fault current they may be briefly exposed to. Protective devices should be rated to carry full fault current (not let through) unless they're in a manufacturer approved series combination.
@dirkgermonprez5035
@dirkgermonprez5035 2 года назад
if we start at 100k and you want to reduce for MCB at 10k, then you have to reduce twice?
@graceyj20
@graceyj20 2 года назад
That depends on the protective device characteristics and the short circuit current sources throughout the system. That said, if you're looking to reduce for a 10KAIC rated MCB you should confirm with the MCB manufacturer that the make/model of the fuse your planing to use is recognized for series rating with that specific MCB.
@alext5497
@alext5497 3 месяца назад
Where does conductor length factor in
@graceyj20
@graceyj20 3 месяца назад
The conductor length/size/properties reduces the fault current from the source to the fuse due to it's impedance. Calculating the available fault current is not covered in this video.
@alext5497
@alext5497 3 месяца назад
@@graceyj20 I was binging and just put the comment on the current vid I was on. Thanks
Далее
Calculate Generator Subtransient Reactance X''
2:54
Просмотров 12 тыс.
🤯 #funny
00:20
Просмотров 1,2 млн
Understanding Fuses
43:28
Просмотров 6 тыс.
Fuses Explained
17:59
Просмотров 44 тыс.
Impedance Explained.
22:35
Просмотров 125 тыс.
I2t. What? Why? When?: The electric fuse case
16:00
Просмотров 4 тыс.
NHP Webinar: Selectivity Part 1
33:21
Просмотров 7 тыс.
Fuses vs circuit breakers
27:03
Просмотров 71 тыс.