How to replace diverter valve . Leaking diverter valve on Baxi Duo Tec / Potterton Promax 

B Heating Service
Подписаться 340
Просмотров 1,8 тыс.
50% 1

How to replace diverter valve / 3 way valve assembly. Leaking diverter valve on Baxi Duo Tec / Potterton Promax boiler step by step
This video is for GAS SAFE ENGINEERS only, always follow manufacturer instructions.
Before to start any work on gas appliance isolate the power, turn off the gas and the waters.
Leaking diverter valve
1. Download manual
www.wolseley.co.uk/wcsstore/E...
2. Remove front cover
3. Isolate the cold water, flow and return valves
4. Drain the boiler
5. Leave open the drain point
6. Remove diverter valve.
7. Reinsert the new diverter valve.
8. Close the drain valve open the flow and return valves.
9. Re-pressurise the heating system till 1 - 1.5 bar

Опубликовано:

 

19 апр 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 10   
@paulrossiter9567
@paulrossiter9567 Месяц назад
You should use the monument spanner 🔧 22 - 15 mm nuts 🤩
@2009bager
@2009bager Месяц назад
Just replace the cartridge and happy days
@bheating
@bheating Месяц назад
The cartridge is not compatible for this type of diverted valve because it's with bypass pipe. www.screwfix.com/p/baxi-7656807-erp-models-3-way-valve-cartridge-without-by-pass-only/291TP?tc=ET6&gad_source=1&gclid=Cj0KCQjw8pKxBhD_ARIsAPrG45na_KR8zPgnN0dwE6cROfAMfpBTLR-C7h6Ky5MeGB-MVvrTYis8XB4aAnizEALw_wcB&gclsrc=aw.ds
@bluedwarf8858
@bluedwarf8858 2 месяца назад
Just wondering why you took the whole block out, i thought you could unscrew the top of the diverter valve and screw in a new one. Im no expert its just what ive seen being done on other channels
@bheating
@bheating 2 месяца назад
The cartridge is not compatible with the tree port valve with bypass pipe. www.screwfix.com/p/baxi-7656807-erp-models-3-way-valve-cartridge-without-by-pass-only/291TP?tc=ET6&gad_source=1&gclid=Cj0KCQjw8pKxBhD_ARIsAPrG45na_KR8zPgnN0dwE6cROfAMfpBTLR-C7h6Ky5MeGB-MVvrTYis8XB4aAnizEALw_wcB&gclsrc=aw.ds
@bluedwarf8858
@bluedwarf8858 2 месяца назад
@@bheating ah OK got you, thanks
@leebuchanan8194
@leebuchanan8194 2 месяца назад
Plus if its snapped you change entire lot anyways,unless you can fish bits out
@davecavaghan7889
@davecavaghan7889 Месяц назад
why didn’t you source a compatible cartridge for the boiler model/ serial number
@bheating
@bheating Месяц назад
For diverter valve with bypass there is no cartridge replacement awalaible.
@dickiedubs3137
@dickiedubs3137 Месяц назад
I'm sure there is, seems like a tough job for a simple cartridge change
Далее
Baxi/potterton promax E133 fault
6:06
Просмотров 22 тыс.
Vaillant EcoTec Diverter Valve Replacement | FULL
27:33
Nurse's dream !! 😂😂
00:17
Просмотров 4,7 млн
Каха и калЪян
00:46
Просмотров 170 тыс.
Baxi duotec leaking diverter valve www.3tgas.co.uk
6:05
Vaillant Ecotec Diverter valve change
14:15
Просмотров 30 тыс.
Potterton Promax
2:24
Просмотров 10 тыс.