@@benzblogsVlogs regarding sa deepsea boss, safe lang ba mag adjust sa synch parameters? 3v gawin ko 5v, phase angle 5 gawin kong 9. 8610mkii deepsea...
Sir im in vacation ahm if the problrm underfrenq. Take a look first is the alarm shows with load or without load now if the alarm shows without load just simply adjust the frequency accordingly to the freq.50/60 hz and also check first whin the engine start if there is voltage ok sir
Bro before what is the nominal voltage before not drop first run without load if voltage is in normal if not check the exciter winding if have resistance thin check the diod if in good condation now if all good thin replace avr
Good morning sir we are having an issue with oye diesel generator, the display says under voltage shutdown and when we start the system it only last like 5 seconds and then it shutsdown again. Thanks for your videos and your time.
Do this first start and check the rpm if stable after that if stable thin check the avr volatge fuses use multi meter to do that if volatge is zero or have 50-vac thin just excite it
@@benzblogsVlogs thank You do much for the quick answer You are saving lifes. I forgot to Say that mantainance team change the batteries with other that migh have a lower amp. That can be a reason too? Thanks again for all this videos !!!!
Ok tool kit ay ginagamit lamang para electronics engine meron suang tinatawag sabihin na nating block box or ecm yan jan natinmagagamit pang program ant pang troubleshoot ang toolkit
Sir ask ko lang po Kung anong irerekomenda magandang magandang libro about sa diesel Generator set.troubleshooting , inspection at Kung saan mga naka locate Yung mga sensor ng Genset .
Why sometimes phase voltage are not balanced with respect to ground. We have one DG where phase B was showing 190V Ac only but other phases are around 230v ac.
Meaning this is 3phase do one thing make a reaistance test every coil but in order to know remove first the connection mostly voltage unbalance is coil problem
@@benzblogsVlogs You're possibly or i can say your correct Sir as we measure different readings on our insulation test. Thank you for your support Sir. More power to your channel.
My friend My DA output is showing 20v, tried to excite the exiciter by external battery, it is developing 110v for the time battery is connected. The generator is of 380 Kw. Any suggestions pls.
Hi Sir. I’ve juste bought an Atlas Copco used generator QAS200 and I have a failure (underfrequency) and the generator doesn’t start. I thought it was batteries which we changed and nothing happened. Can you help to troubleshoot please ?
Ok there is lots of reason first is the load my be hundred percent load directly or your configuration is went wrong or check the alarm so we can point out what going on!
sir gud am, what are problem if my gen set running only an hour after drop into 90 volts and the frequency goes up,almost more than 70hz after drop to 90 volts.thanks, god bless
Now if you connected correctly positive and nigative to exciter and still give low voltage means ither your exciter is defective or the alternator itself have problem
sir gud pm po, yung cummins generator 6cta 8.3 new calibrate po injection pump pero pag my load hirap po xa pati load bank namamatay po ano pong problema ng ganung case..thanks po
Boss tanong lng kc genset nmin under voltage din..ok nman Po ung hrz & RPM at reading Ng voltage, kaso pag niload na Po Nmin bgo sia Ng under voltage.salamat Sana masagot nio ang Amin katanongan. Maraming salamat Po.
Sir pag over voltage ganito lang gawin mo start mo check ko line to line ang voltage at ano ba ang nominal na nakaprog sa module at check mo din mga fuse
Fail to start sir pwedimg hinangin mgbleed ka sa fuel check ko if my fuel return and thin check duel relay is active during cranking make sure suply is distributed correctly
Ok po fuel system aandar po sya infew second at magshutdown sometime ang alarm nya under voltage sometime fail to start sir pero pag tinanggal mo sa fuel solinoid aandar sya thanks po
Sir good day to you sir make aure rpm in a good condation if it is high voltage and the engine is normal just adjaut in your AVR in order to fix the problem
Ah ok sir if your engine mechanical or conventional normal that the frequency is 62 hz but if electronic should be 60hz but mean while if you talk about unbalance load you have to refer that to your load connection
@@benzblogsVlogs san ko makikita ang charging Alt sir. Currently naka power up ung genset without load para ma check ko kung sa genset ba o sa load ang problem. DSE 6110 MKll panel
sir good day po,yung magnetic pick up po bh may tendency din na ma dumihan at numipis kaya hindi gagana..tsaka ilan yung specific volt nya para gumana..salamat po
Hi Sir , our generator Cummins brand 169Kva always shutdowns everytime we run for a minute. It shows under voltage alarm. What could be the possible problem? Kindly help. Thank you
Ok undervoltage means voltage its below from nominal voltage now till me what is the output of the voltage and make sure all the fuse from your sensing line is all in good condation
Sir, my 1000KVA / 400V /50hz cummins genset kami, amg controller nya deepsea 8610 MKII, low voltage sya 10V lang na produced pero reached nya rated speed. Nacheck ko na ung rotating diode goods naman, nag excite ako ayaw mag build up ng voltage, nacheck ko na ung + at - ng exciter may 12ohms naman. Ok naman mga fuse at wire connection, ano kaya problema??
Nong ng excite ka gomamit kaba ng multimter para sukatin ang boltahi or doon kalang ng check sa module? Answer first para maidentify ang prob thank you
@@benzblogsVlogs nag produced sya ng voltage nung binaligtad ko ung postive at negative ng excitor sa avr, tapos binalik ko sa original position. Nag produced na sya ng 400V, kaya nagtaka ako bakit ganun, eh original connection nya un since nabili ng company namin ung gen.set. ngaun po, nag synchronized ako at amg load umabot sa 390A which is balance naman sa ibang gen.set. yung nag increasr ng load, pumutok ung fuse ng AVR. Ano kaya problema?? Pangalawang beses na un na pumutok fuse. Ok naman mga wiring walang grounded, pati excitor ok din. Posible kaya na low insulation na ung alternator windings? Mainit din ung body ng alternator
@@benzblogsVlogs posibly po ba mangyari un na binaligtaf ung exciter saka lang sya nag produce ng 400V, tapos binalik sa dati position ung terminal ng excitor, Ok na sya. Un lang, ung tumaas ung load, pumutok ulit ung fuse ng avr
Ganyan ang nangyari sa genset ko brad Under Low voltage yng lumalabas sa module ay 360v lng kaya namamatay pro check ko ang main wire nyan bro yng 3phase at single phase ok naman ang kuryinti nya 416v ang 3phase at 230v naman ang single phase ano kaya yon brad ang sira module sguro or kailangan i adjust ang setting
Make sure lang sir na sa viltage sensing side is same na voltage nag nababasa mo sa tester doon sa breaker side if parihu thin there wrong with ither program or a wirng problem only
If you want to make 400volt ac shout be your alternator is 12leads in order to convert the wiring to series Y to prduce the volatge 400but your need to re connect your avr connection and to change to configuration from your module in order to work
Hi Sir good day to you I am tapas from banglades FG wilson 50kva diesel generator Un load generator voltage L-N 235volt, frequency 49.80hz & load L1-10amp,222volt,49.4hz,L2-15amp,218volt,49.3hz,L3-35amp,180volt,48.9Hz then generator shutdown so what problem.... Please sir urgent case
Sir high volatge alrm always i ask to check if engine speed if stabel thin check the avr volatge now if all ok at zelo load this. Only config you need after that put over and under voltage delay your prob solve
@@benzblogsVlogs Thank you sir. We will try your suggestions. But if the AVR are faulty, can we replace it with different type of AVR? like a generator set with shunt excitation alternator and a Stamford AS440 AVR to a Stamford MX321 AVR with pmg type of excitation?
Bus not live meaning there is no voltage going to your module buss sensing make sure also the the aux contact is working properly for feedback going bact to the module
Off tge breaker run the generator adjust the voltage in tge avr using the voltage potentiomter there in the avr use multimeter to measure the voltage if its blance its always have variation 1-2 deferences
Gud pm sir, panu po ba i troubleshoot pag ang indicate po ay "electrical tripp" note 500kva gen set po and gendiesel po ang brand, thank you po sa sagot
Onang tingnan mo is my nakainstall ba young breaker mo na shuntrip if meron nakaprogram yan sa module at may isanag relay yan para sa trip ng breaker mo
@@benzblogsVlogs Oo nga pala Sir,motorized xa,nka synco pala,kaso d kuna pinagana isa, dahil maliit nlng load,tsaka may sira dn..cge Sir salamat,nka subscribe nko sau Sir hehehe
Sir ganito yan loading voltage not reach ano ba ang bolatge ouput na nalabas sa generator mo ngayun kc halimbawa 400 ang ac before ang configuration tapos ngayun ang output lang ay 380 lang hindi inabot you g loading na 400
Pasensiya sir pero hindi ko nakunan ng video pero ganun yung pangyayari. Kung baga eh nag bigay siya ng generator over voltage tapos nag adjust kami sa AVR pero ganun pa din alarm na binibigay niya. Hindi kaya sa AVR ang problema?
Ganito mona sir paandarin mo teaterin mo sa module yung voltage sensing ng module if my voltage kong wala check ko fuses kong my busted now kong ok at ganon padin check mo fuse ng avr at kong ok at same walang voltage mg excite kna okay
Hello sir i have weserbeke 11.0BDT it was running good after long time not start no output voltage from alternator zero volt when I'm giving excitation 12 vdc voltage coming 25-30 voltage only and then when i remove excitation Voltage coming back same as before to zero please help me how to solve it