@@benzblogsVlogs Yon lang, kala ko nga mag stay ka pa ng mahaba haba para mabawi yong 15days na quarantine mo. Anyhow importante nakapiling mo ang family for even short days lang.
Sir idol.. may kinabit ako na Smartgen controller lalabas lagi ung over frequency alarm.. ung nasa default parameter settings list nya ay na 57hz.. pwede k😅 ba cya itaas sa 60 hz kc frequency measured nya ay 61 hz. sa display nya.. wala kc ako driver software sa laptop hirap hagilapin sa net ung driver nya
Hi mate Thanks for your video Can you help me with advice My generator is shutting down under frequency when I'm applying quick load. When load increases slowly- it is working stable. With fuel line everything is ok. AVR new, pump new, infectors also new. Magnetic Pickups new. Voltage is stable.
In this problem just add 5sec Delay in your freq under and over and also from your voltage add 5sec over and under so it has time recover during shock load or sudden load
Sir, ung cummins engine namin 1000KVA using DSE8610 MKII, nag over frequency, ang rating ng speed 1500rpm pero umaabot ng 1600RPM tapos ung ampere nya nag up & down na dahil sa over speed, taposag shutdown na alarm Over Frequency kasi over speed
@@benzblogsVlogsang meron lang sa speed controller: run, idle speed, gain at droop. Nag try nako ng ibat ibang adjustment, pag nilalagyan sya ng load, nag hunting na.
Sir nakakaapekto po ba pag bumaba rpm ng generator baba din po ba ang hertz po? Example 1800 rpm 60hz Ngayon po 1731 rpm 57 hz po. Cummins generator gamit po namin
sir ano pwedi gawin pag low frequency paano po mag adjust sa AVR ng Magnaplus model MP-220-4A .sana po meron video sa sagot para mag maintindihan ko thank po.
hello , can you tell me what can cause the surge arrester (installed with bridge diode) to burn out? and why it's installed, or In other words what can cause voltage spikes?
Trouble shooting is not just easy and short operation you need time to find the problem and to fix it and trouble shooting has no shortcut i hope you understand that have a bless day to you sir
If over voltage sir ganito ang una mong almin voltage output ng generator mo thin check mo ang confige ng module if tma amg nominal okay thin update me if anong nka config
Sir. Patanong naman kung bakit nagpa fluctuate ang voltage sa voltmeter.. pati mga ilaw ay kumukurap sabay sa voltmeter. Nag check ako sa diode ok naman.. posible kaya na avr ang sira? 10 kva po pala generator ko assemble sa pinas.. yung ang engine ay 3 cylinder kubota na diesel. At mindong ang kanyang generator motor. Thanks.🙏🙏🙏
@@benzblogsVlogs thank you sir! try ko and check. 2 minutes lang sir nag under frequency normal naman ung rpm nasa 1800 and 60 hz. but no load. we will try to load sir. tnx
sir....ung frequency ng generator nmin taas baba...may sensor po ba na maaring palitan o maaring nasira..na kailangan palitan...salamat po...good day....
I have a 30kw generator single phase and when I turn on air conditioning the voltage drops from 248 to 170 in 1to 2 seconds but in that time computers shut down due to low voltage. What could be the problem. Before it was not doing that. Exciter was rewinded and have voltage of 248 L1 L2 and 128 L1 N. why voltage drops
Pwedi yan unbalanace kadalasan sa pinas na problima sa mga 3phase gnset mataas ang isang load na linya kaya over current agad kahit dipa abot ang full kapacity ng generator
Sir benz Tanong lang po Yung generator Namin pag Wala pang load normal Ang voltage nya pag nilagyan na Ng load Minsan nag over voltage na, ano po cause nito at pano ayusin?
Thank you so much sir,how software can be got,please give us the idea,,we submit the request. But we don't get the confirmation email,does it require some cost???,sir you can help
Yes sir I did but till now ,when I regain do it, they tell me that I have to fill the form ,with the email from deep sea,but that confirmation e-mail i never got,they always tell me that my request is still processing,I have the generator have the problem of over frequency but some time it run correctly at required speed but when I shut it down ,and I restart it again it comes in an over speed mode,so does it requires again re setting of deep sea controller ,the reason why ineeded the soft to see how ican trouble shot that error ,thank you sir
Kong 11 voltage lang makikta sa module make sure fuse sensing id all not busted avr fuse ng busted thin try to do exitation but remove first the the volatge sensing from your avr during process
If you are in place where you don't have computer to configure under frequency, how can I do it manually? I have 60kva Generator always showing under frequency and can AVR cause it?
Sir magandang gabi po... I hope matolongan mo ako. Smart gen ko kac nag aalarm under frequency alarm. Mamatay pero mga 5starting totoloy na ang undar. Kailangan pa painitin ng husto para mag toloy ang andar niya.
And if your engine is electronic or have a speed controller do it to stablize first the engine coz useles doing the avr stability of your wnhine is not
There are two thing you can fucos 1.monitor your voltage the load ither over load kw if voltage down due to shockload its also shutdown under frq 2.manitor the speed or rpm of your engine if unstable its also shutdown under freq
my trouble kmi dito sir low voltage 50vlts lng sya tapos 10sec.shutdown sya.pano ba mgcheck ng AVR if sira na sir.sample lng sa output and input power sa ignition lang not running
Sir ganito lang excite nyo mona kong tumaas ng 300-500 vac meaning ok pa yung alternator nyo tapos balik nyo ivr connection of same happen thin replace avr
@@benzblogsVlogsmay isang transparent fuse sa AVR assy.my 3 diin sa likod ng panel board saka dalawa para sa ignition.pag on ng ignition myron naba supply agad sa avr sir na DC volts
Ngayun kong walang voltage ibigsbihin double check mo yung fuses or breake bka my pumotk or nag trip doon sa senssing side ng module at ng avr mo mostly yan ang kadalasang nangyayari
I have cummins 1250kVA engine and when I conduct Loadbank test from 75%load going to 100% load when at 970kw load the generator alarm and shows fault "SpdRegLim" and the rpm and load decrease suddenly fast.
Make sure your AVRI have correct connection and correct supply now there is light indicatore if red meaning there wrong if green is ok double check that and message me if u check
Bro under frequency is related to your voltage under freq means you voltage is under also so juat adjast the volage to the correct setting accordingly thin frequency will be adjusted automatically
Kc pag volatge is low dapat low din freq. mo baka mataas yung rpm mo ok po kong ganyan ang problima unahin nyo mona e solve ang speed para doon na tayo mg fucoz sa alternator
Underspeed sir lagi g tingan nan ang fuel line kong may singaw or leakage thin lagi g check ang fuel baka may halonv water na sa tangke or madumi na mga filter po
Sir may tatlong teadon jan ither this 3 ok 1 pweding mataas ang volatge mo apiktado yan 2 pweding sa rpm or speed masyadong mataas ang speed hindi tugma sa module setting 3 configuration not properly config double check
This software are same about avr stamford AS440? My generator issue is generator under frequency like same the video, but i will set the frequency on 50hz. Where im to download the software for configure issue generator under frequency sir? Thank you
Ganito sir kong no generator freq ibigsabihin wala kading voltahe ngayun check mo mona mga fuse or breaker man mga connection baka nagloose lang if ok naman ngayun testerin mo kong may voltahi if wala magexcite kana para malaman natin kong avr lang sira
Hello sir. Advice me . My generator shuts down when utility power is off and on auto mode due to overfrequency alarm deepsea 6120mkiii. Can low temperature of engine cause overfrequency alarm
This is possibility that happen due to colf weather but make sure heated up during engine fire up make sure that there is proper delay for over freq and volatge
Sir patulong, bagong palit ng AVR ang DG namin. Upon running without load all parameters are in normal condition but when applied with load output frequency gets high. Any inputs? Mechanical engine
Just adjust the stability during adjustment nees multi meter to do it now put your multimeter to voltage thin adjust ither clockwise or counter clockwise now put little load like 5-10 kw thin adjust till atable
@@benzblogsVlogs Ayy Praise God bro yng Genset ko kasi nagloko ngyn ehhh...tumataas at bumababa ang kanyang RPM hanggang sa nagshout down at ang lumabas sa monitor ay Gen.set under freq.alarm
@@benzblogsVlogs 380kva sir commens....kanina kasi taas baba taas baba kasi ang RPM nya hanggang sa bumaba nlng siya at namatay at yon lumabas ang genset under freq.alarm
@@benzblogsVlogs good day sir, i have situation that generator doesn't start all the way, it shutdown after 15secs. and ECU red is warning, what do you think is the cause?
Ngayun pag unang andar normal naman at pagnagkaroon ngload ng over voltage sya dahil yan sa impact load ngayun kong ganyan ang naging problima mo you need to follow tgat config. For the time delay
@@benzblogsVlogs yes pag nagload siya saka nagka alarma ng over frequency pero di mag off ang genset normal nman ang voltahe 230volts slamat sa sagot sir
Sir patulong naman po.ano po ba pwedeng troubleshot ng genset kapag namamatay bigla at Ang Alam nya ay frequency at hard starting na sya mga 3-4 na crank before to start and after mga 30mins or more namamatay ulit sya.pahinge naman ng advise po sir
Thankyou so much sir ... Ramping pala tawag sa ganun. Dami kasing pinihit ng mga nauna saking maintenance. Sa vids mo din po natutunan ko pati pag adjust ng under volt. Welder po ako kaso my kunting knowledge ako sa electrical kaya ako n rin naging maintenance ng company ko. Salamat po sa mga vlog mo. Daming nadagdag sa kaalaman ko
Sir ganito pweding marumi na ang fuel filter mo linisan mo or preventive maintenance mona yan kc kasama ng bunaksak rom mo check mo din baka lagpas kana sa kapacity ng genset load mo
Sir your 5kva is only 4kw wich equivalent 18 amp full amp your generator 1hp its equivalent 5amp times 2 mean 10+ amp load shock load wich deficulties to your to your 5kva