Wiring a meter, main and sub panel for rough in inspection!  

The Kelley's Country Life
Подписаться 152 тыс.
Просмотров 119 тыс.
50% 1

In this episode I wire up my meter box, main panel and sub panel for my upcoming rough in electrical inspection. CHECK YOUR LOCAL CODE, IF IN DOUBT WITH ELECTRICAL YOU NEED TO HIRE A QUALIFIED ELECTRICIAN.
Our merchandise, thank you for the support www.bonfire.com/the-kelleys-m...
The thinker tinkerer shirt www.bonfire.com/the-kelleys-c...
GOT ICE? shirts www.bonfire.com/the-kelleys-c...
This is our Amazon store with affiliate links to the products we use on the channel. It doesn't cost you anymore and it helps support the channel, THANKS!
www.amazon.com/shop/thekelley...
For any hunting or fishing needs, visit our sponsor for some of the best deals in outdoor gear. This is an affiliate link costing you nothing extra, but does help support our channel. Thanks! www.sportsmansoutfitters.com/...
View out other channel for outdoor related content such as fishing, boating and hunting! / @tkoutdoors
Our Facebook / the-kelleys-country-li...
For business inquires please contact us at kelleyscountry@gmail.com
The Kelley's Country Life LLC accepts no responsibility for you trying anything you see on our show.
Our address
6244 East Caps
PO Box 22
Lamont, FL 32336

Опубликовано:

 

25 окт 2021

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 216   
@alanmcrae8594
@alanmcrae8594 3 дня назад
Excellent presentation! Step by step, clear view of procedures, verbal clarifications, and no annoying background music. This is how to help people to diy. RU-vidrs take note...
@TKCL
@TKCL 3 дня назад
Glad you enjoyed it
@LinksterGaming
@LinksterGaming 10 месяцев назад
I just did my rough in for my plumbing, electrical, and HVAC on my first house. Done everything myself and passed inspection last friday. Its definitely a journey.
@TKCL
@TKCL 10 месяцев назад
Congratulations! That's a huge step!
@LinksterGaming
@LinksterGaming 10 месяцев назад
@TKCL thanks, I was definitely nervous. I've done a lot of work with new construction, but those 3 were the only things I didn't have experience with. It's should be smooth sailing for me here on out. Just a matter of time and money.
@80carheros
@80carheros 2 года назад
As a journeyman electrician, I must commend you on your use of code. You did everything very well, better than some electricians.
@TKCL
@TKCL 2 года назад
Thank you, I've spent a lot of time doing my best to read the NEC and learn.
@jfromtn7410
@jfromtn7410 Год назад
hey did you use a ditch witch to run3 inch conduit
@TKCL
@TKCL Год назад
Yes, best $75 I ever spent. My conduit was 2.5 inches.
@frogdad25
@frogdad25 Год назад
@@TKCL Where can I get a NEC???
@TKCL
@TKCL Год назад
All NEC regulations are on the internet, or you can buy a rule book.
@gregorythomas333
@gregorythomas333 2 года назад
Just a small tip: For finding wiring you can check with your local metal recycling centers...most utilities will sell their ends & scraps to them and you can get it for pennies! I worked at one for a while and noticed the power company would bring the left over "bits" to us...these bits would be up to several yards long...a very nice size for stuff like this.
@markcaldwell1245
@markcaldwell1245 2 года назад
To bend the ends of large wire use a deep socket the size of the wire with an 18” extension.
@TKCL
@TKCL 2 года назад
Good tip!
@mikeerstad4828
@mikeerstad4828 2 года назад
As always GREAT JOB Andrew! Pretty sure you will pass your rough in inspections with flying colors!! One thin for sure any issues arise with your house you will know exactly where to start troubleshooting.
@TKCL
@TKCL 2 года назад
That's exactly right
@highryder100
@highryder100 2 года назад
You should check out ground crimps.. they come in different sizes and you can leave 2,3,4 grounds long to go to each switch.. saves valuable space in those tight boxes
@bryanripple1938
@bryanripple1938 2 года назад
Great learning video Andrew. I have gotten a lot of great information and your videos are always a highlight for my days. Looking forward to seeing what the inspector had to say.
@TKCL
@TKCL 2 года назад
Thank you very much Bryan!
@rongray4847
@rongray4847 2 года назад
Well Andrew as far as I am concerned you hit it out of the park again. I could not have done what you are doing. Very interesting. Thank you !! Take care and have a good week. 🇨🇦
@TKCL
@TKCL 2 года назад
Thank you sir!
@hrlee2381
@hrlee2381 2 года назад
You are doing an amazing job on your home. You have to start somewhere and you are doing great. Good luck on your upcoming inspections.
@TKCL
@TKCL 2 года назад
Thank you very much
@jonathangreenawalt5724
@jonathangreenawalt5724 2 года назад
For the hard to reach areas, the pro level foam wand thats stiff aluminum, attach vinyl tubing so you can foam in corners, around pipes, and really hard to reach areas.
@janetraulerson1590
@janetraulerson1590 2 года назад
Enjoy each of your episodes. I have learned so much....Thank you!
@TKCL
@TKCL 2 года назад
Thank you for watching
@barbaraharrold5361
@barbaraharrold5361 2 года назад
Oh how exciting!!!! I’m sure you passed with flying colors:) I need to hurry and get to the next video to see how it went:) tfs:)
@bobgray617
@bobgray617 2 года назад
That looked like a tremendous amount of work you pulled off in this video. Awesome job.
@TKCL
@TKCL 2 года назад
Thank you, it was a couple of days worth.
@huntingandfishinglittlebit3715
@huntingandfishinglittlebit3715 2 года назад
Praying that everything pass keep the good work up.
@workingmanrondoyle3287
@workingmanrondoyle3287 2 года назад
Another great video Andrew 👍 I knew this is after the fact but Buchanan's sleeves would have helped you tremendously at your switch box locations for multiple bare copper pigtails. I only use greenies on my duplex outlets and single switch box locations. Good luck on your inspection, my brother!
@TKCL
@TKCL 2 года назад
Yeah I'm just learning about those... Oh well, I'll make it work.
@johnsmithson2506
@johnsmithson2506 Год назад
Looking good keep it up always exciting if you love what you do I grow up around that kind of work and still doing it today I love it that days seems like they get shorter doing it if you know what I'm saying just past so fast like whating you video !!! I look out for the next one can't wait to see you pass inspector inspection lol.
@TKCL
@TKCL Год назад
All is well what a learning experience it was building our own home. Took 13 months and I learned so many great skills.
@vtech6885
@vtech6885 2 года назад
Just a suggestion, you may want to add a block to space out the two kitchen switch boxes by the door. When you go put the cover plates on there going to be really close. And because your OCD like me, you will notice it. Better to do it now.
@seymourscagnetti1413
@seymourscagnetti1413 Год назад
Great eye for the little details! He could even flip the box 180° and nail it to the stud to the right. Either way, even if the finish plates don't touch, it's too close and won't look right.
@JimmyHensley36
@JimmyHensley36 2 года назад
Great job and like a lot of work . You getting there . Can’t wait to see it sheet rock in . Gonna really make a big difference. 👍🏼👍🏼👍🏼
@TKCL
@TKCL 2 года назад
Yes it is! Thanks for watching
@JimmyHensley36
@JimmyHensley36 2 года назад
@@TKCL sent u an email ..
@TKCL
@TKCL 2 года назад
I responded
@knuckle47
@knuckle47 2 года назад
Given that crap with the bank, I think you’re going to be happier and enjoy the drive you have now to make all of this tie together… wishing you all the best !
@TKCL
@TKCL 2 года назад
I agree! Thanks
@waltmooredanwilson8754
@waltmooredanwilson8754 Год назад
Great job Andrew with the work and the video. Just one little tip on putting those ground rods in that might help you in the future. What I use is a very powerful SDS rotary hammer drill. I put a pointed bit in it, slip an impact socket over that and drive the rods in with ease. I just thought that might be helpful. Take care and God Bless.
@TKCL
@TKCL Год назад
I own a smaller hammer drill, thanks.
@samclements2834
@samclements2834 2 года назад
Amazing man!! So excited for you both!!
@TKCL
@TKCL 2 года назад
Thank you
@davek6630
@davek6630 2 года назад
For you or your viewers on future installation of a meter socket and an outdoor sub panel, you can get a combo panel that has the meter socket/outdoor panel in one package. You still have an indoor panel also. They are great because you don’t have to deal with all the stuff wire.
@TKCL
@TKCL 2 года назад
I discussed that in a previous episode, none available locally and to order one online with the proper size breaker was going to be an additional 200 dollars over the setup you see here.
@pampilgrim2274
@pampilgrim2274 2 года назад
Hi, Andrew! This was quite a hard day’s work. You did great as always.
@TKCL
@TKCL 2 года назад
Thank you very much
@russrockino-rr0864
@russrockino-rr0864 Год назад
If your City, County, etc allows it, I would install the grounding electrode conductor to the main panel inside the house. That way, if there is ever an issue or failure with the connection, the seal on the Meter Base does not have to be cut. For the Homeowner, this can be an ugly and time consuming process dealing with the power company and/or inspector. You may not be able to get your power back on the same day. If the connection is in the Main panel, you can do the maintenance without any power disruptions. Drill a hole through the wall and run the grounding electrode conductor{conductor for ground rods} to the main panel. Mount a bonding bridge on the outside wall near where the GEC comes through for your low voltage grounds. Great video, Thanks, Russ, J.Electrician from Oregon
@TKCL
@TKCL Год назад
After inspection my inspector required grounding at the meter box. Apparently my Electric Co-op requires that as well.
@johnnyfrazier2698
@johnnyfrazier2698 2 года назад
Good luck on your inspections
@joebufford2972
@joebufford2972 2 года назад
I had to chuckle when you started bending those thick wires cuz I know they don't bend! hang in there Andrew you got this one.
@TKCL
@TKCL 2 года назад
Lol I eventually bent them, but they didn't like it!
@kevinjmoore2359
@kevinjmoore2359 2 года назад
I have been following you for quite some time. I worked as an Electrician for 40 years and I wanted to tell you that you are doin a great job. I am sorry I did not tell you about the LB's you were going to hide in the wall. I thought maybe that wall was going to be open.
@TKCL
@TKCL 2 года назад
I have a feeling it would have been a non issue, but I chose to tear it out and install the SER cable. Thank you for watching!
@joshruby
@joshruby 2 года назад
here in nc our sub panels have to have separate grounds and neutrals like yours but it also requires a ground rod in the ground.
@bradbrescia
@bradbrescia 2 года назад
When I was a kid, my parents would only watch HGTV (before it turned to reality TV) and PBS and the never-ending episodes of This Old House, The New Yankee Workshop etc. I could NEVER understand what they found entertaining about that. Yet, here I am, 25 years later getting a soup-to-nuts tutorial on building a house and couldn't be more entertained. So glad I found your channel when I did. I can't wait to see what the inspector said. Keep up the great work!!
@TKCL
@TKCL 2 года назад
Lol, don't forget about the Red Green show.... The ultimate handyman! 😂
@TKCL
@TKCL 2 года назад
Thank you for watching and the support
@jamesscroggins3486
@jamesscroggins3486 2 года назад
Awesome work, I am excited to see how you did
@TKCL
@TKCL 2 года назад
Thank you!
@gaylewatkins4685
@gaylewatkins4685 2 года назад
Hello Andrew 🙂 All of the wires started to look like spaghetti to me. I'm impressed with the concentration you needed to connect all of the electrical. Great job as always. God Bless.
@TKCL
@TKCL 2 года назад
Lol well I like spaghetti!
@ethanclement9647
@ethanclement9647 Год назад
One thing I learned early in the game of roughing in is to get the bare copper ground wires tucked into the back of each box to make room for the hot and neutral wires. Always seems to work for me. As far as the feeder wires go there are bending tools that make handling those thicker conductors the whole lot easier.
@gustavocervantes5435
@gustavocervantes5435 7 месяцев назад
Hey bro you did a great job thank you for sharing with us amigo! God bless you🙏
@TKCL
@TKCL 7 месяцев назад
Glad you enjoyed it, God bless.
@MJADoingStuff
@MJADoingStuff 2 года назад
Thanks for the video getting ready to install a meter and main panel in the pole barn. Also glad you decided to start wearing a hat 😁👍 I know they give you head aches but the sun will make you start looking old quick.😂
@TKCL
@TKCL 2 года назад
Glad you find the content useful. Take care
@thtadthtshldntbe
@thtadthtshldntbe 2 года назад
Pro Tip, if you ever do anything like dealing with the heavy gauge wire bends again, before you attach the panel to the wall, temp attach it to a heavy work bench, do not cut the wire to length yet and you can do most of the needed bending of that section via test fit using heavy duty tools that you cannot use near the installed box due to spacing. One of my uncles, years ago, had something jury rigged up used metal conduit of the size appropriate to the wire. He had like 1 inch or so segments that were welded inside some custom steel holders. He would put them on the wire about half an inch or so apart and then screw the steel bars attached to the conduit to this repositional jig that he could set to any curvature and then he would plug the compressor in and it would bend to the target shape. Another thing, that my GC uncle who did electrical as well would do is put the heavier gauge wire in metal conduit and then stick that in a conduit/rebar bender.
@TKCL
@TKCL 2 года назад
Good tips!
@hrlee2381
@hrlee2381 2 года назад
That's a lot of wires. Wow. What a puzzle.
@ryanzynda5114
@ryanzynda5114 2 года назад
The house is looking awsome.
@TKCL
@TKCL 2 года назад
Thanks
@andrewbreiter-wu
@andrewbreiter-wu 2 года назад
Duct seal is approved more than silicone. Had an inspector requires we scrape silicone off and duct seal in the hold instead. Some can be very picky even without basis
@danielfuentes9884
@danielfuentes9884 Год назад
Great teaching 👍
@TKCL
@TKCL Год назад
Glad you found it useful.
@jeremiahs45
@jeremiahs45 2 года назад
We carried a 1” box wrench to bend service cable. Personally don’t like the ground wire nuts. I will stick with bare copper crimp sleeves
@lloydwilliams8715
@lloydwilliams8715 2 года назад
Ha Andrew. Checking in from Jamaica 🇯🇲🙏. Let's get some box and wires installed ☺️☺️
@TKCL
@TKCL 2 года назад
Yes sir! Take care
@lloydwilliams8715
@lloydwilliams8715 2 года назад
@@TKCL thanks Andrew, am really impressed with the way u are building, been your first. Keep it up. Looking forward to the complete project.
@TKCL
@TKCL 2 года назад
Thank you very much
@josmith5459
@josmith5459 Год назад
Thanks for the awesome video lots of info and nice neat job you did.
@TKCL
@TKCL Год назад
Thank you for watching
@shanepadgettii9784
@shanepadgettii9784 2 года назад
You hitting that ground rod so close to that Siding made me so nervous 😓 . Great video and good luck on inspection!
@TKCL
@TKCL 2 года назад
Should have seen the one I was pounding in right in front of the window 😳
@jacksondavis5746
@jacksondavis5746 2 года назад
You’re gonna hate life especially when you go to land your grounds. Always in my book the grounds and what neutrals you don’t need for arc fault and ground fault breakers. Just makes in tighter and neat behind the service entrance conductors
@mfd4505
@mfd4505 2 года назад
I always land grounds and neutrals first, as said, to get closer and more compact in panel. Don’t forget to leave a ground pigtail for each receptacle and switch, never mind you covered it.
@reneemontgomeryvoice
@reneemontgomeryvoice Год назад
This channel is great! I have watched several of the videos and I am completely amazed how you all built your own home. How did you learn to do all of this?
@TKCL
@TKCL Год назад
Just went after it and researched on RU-vid. I've grown up in the country where you have to figure things out and saving money is a way of life.
@brendaanderson8565
@brendaanderson8565 2 года назад
Looking good.
@TKCL
@TKCL 2 года назад
Thanks 👍
@kingwood4357
@kingwood4357 2 года назад
Can't wait to hear the results of your inspections, I'm really impressed with all that you know or learned building your house, especially electrical and plumbing. Hopping for nothing but minor issues from inspector, Good Luck. .
@TKCL
@TKCL 2 года назад
Thank you very much, editing the video now!
@texasproud3332
@texasproud3332 2 года назад
As we have said electricians are generally first ones in and last ones out
@ArizonaHighDesertHomestead
@ArizonaHighDesertHomestead 2 года назад
Great video.. nice work
@TKCL
@TKCL 2 года назад
Thank you
@WiSeNhEiMeR-1369
@WiSeNhEiMeR-1369 Год назад
HOWdy Kelley's Thanks COOP the WiSeNhEiMeR from Richmond, INDIANA ...
@stuartkorte1642
@stuartkorte1642 11 месяцев назад
What gauge wire did they run from power pole to meter and what gauge did you use from meter to panel? I have to run 4/0,4/0,2/0 from pole to meter.
@TKCL
@TKCL 11 месяцев назад
I am not sure, they provided it. Here everyone calls it 200 amp service cable.
@RedRiverRedNeck309
@RedRiverRedNeck309 2 года назад
Andrew what about a surge protector breaker for your main panel, are you going to install one to protect the whole house?
@TKCL
@TKCL 2 года назад
Yes I am, that's another reason I wanted to free up some space in the main panel with a sub panel
@danielkofman4592
@danielkofman4592 9 месяцев назад
Did you use #2 Aluminum SER wire for the 100 amp sub panel?
@TKCL
@TKCL 9 месяцев назад
Thanks to covid I couldn't find any service entrance wire anywhere. So I had to run standard 2-2-2-4 aluminum wire and place in Conduit.
@mcarroll598
@mcarroll598 Год назад
Did you use an expansion fitting on that conduit coming out of the ground to the bottom of your meter base?
@Qazxswer68
@Qazxswer68 Год назад
Didn’t look like it. That caught my eye too. That pipe will be baking in the sun.
@andrewmott3337
@andrewmott3337 Год назад
What are the sleeves on the wall that go through the back of the panel for the wire?
@TKCL
@TKCL Год назад
Conduit nipples with threaded ends for wire chafes and nuts.
@dougdavis4439
@dougdavis4439 2 года назад
Thanks!
@dougdavis4439
@dougdavis4439 2 года назад
That sure was a lot of work on the electrical! Appreciate the information Andrew. One step closer my friend!
@TKCL
@TKCL 2 года назад
Thank you very much sir! Hope you are doing well.
@Max-cd7xd
@Max-cd7xd 2 года назад
box end wrench to bend it helps
@TKCL
@TKCL 2 года назад
Yes true, good tip!
@user-if1wt9mo3o
@user-if1wt9mo3o 9 месяцев назад
My question is if i add 125 amp subpanel to my 200 amp panel does that only leave me 75 amps for my house. Will it overload my house panel
@TKCL
@TKCL 9 месяцев назад
No, you can add as many sub panels as you want. 200 amps of 240 volt is 400 amps of 120 volt. It's highly unlikely you will ever come close to half of that amount of usage. Most homes run on a fraction of the supplied power.
@21gonza21
@21gonza21 2 года назад
How can you do all this and record?? Awesome work man, there is nothing like doing the work your self, peace of mind no corners where cut.. I know you are not an electrician but I thought Id still ask.. My main panel is inside the kitchen and and the meter is right outside and is about a foot apart, does code require rigid metal conduit or can I get by with plastic?
@TKCL
@TKCL 2 года назад
I've done both with metal and plastic, passed both times. No matter what you use (especially) metal, make sure to put that bushing on the end so the wire can't be cut. Also code usually requires a disconnect switch between the outdoor meter and main panel. My local building department does not require this as long as they are back to back as you described.
@apollorobb
@apollorobb 2 года назад
The lugs in MBR and Meter bases should be torqued with a torque wrench . Shes lookn nice
@TKCL
@TKCL 2 года назад
👍
@mikebarber1
@mikebarber1 2 года назад
Click - Torque achieved.
@TKCL
@TKCL 2 года назад
I'd be curious as to how many electricians actually carry around a torque wrench and torque to specs. I'm betting less than 1 percent.
@instanoodles
@instanoodles 2 года назад
@@TKCL I heard my electricians torque wrench clicking when I had my meter upgraded
@TKCL
@TKCL 2 года назад
You had a rarity I'm assuming, I've seen this topic on popular RU-vid electrical channels and forums. The general consensus is most electricians don't torque to spec. I'm definitely not disagreeing, it's a great thing to do.
@johncastillo2581
@johncastillo2581 Год назад
Is it needed to run the ground wire from main panel to meter socket? aren’t they connected together with neutral so all you would need is run a ground wire from meter socket ground lug to ground rod? Doing my house and trying to learn.
@TKCL
@TKCL Год назад
That's correct and all you need to do. Some areas require grounding at the main panel. Mine requires grounding at the meter. The neutral does continue the bond inside.
@GeronimoChannel
@GeronimoChannel 3 месяца назад
@@TKCL so the correction was removing the bare wire that connected the meter box with the main panel or removing the bonding screw? Or both? 😅. Or something else that I didn’t catch? Thanks!
@NorRavel
@NorRavel 2 года назад
Hummm..... was that a "Stranded" ground electrode conductor that you buried?
@TKCL
@TKCL 2 года назад
Your point? Nec lists stranded copper for GECs. Copper is copper right?
@stickfigure9662
@stickfigure9662 Год назад
Andrew...were you allowed to backfill your trench before the inspection? I'm about to do a similar project and didn't know if inspector has to verify trench depth or do they take the homeowners word for it.
@TKCL
@TKCL Год назад
Yes except I was asked to leave both ends open for visual inspection of depth. Some inspectors will also bring a metal rod to randomly poke at different areas and measure depth to top of the conduit.
@lanelangford5589
@lanelangford5589 2 года назад
Love the show! Take a break!
@willpartin622
@willpartin622 11 месяцев назад
HELP! I'm replacing an old Federal Pacific 100-amp panel with a 200-amp Square D Hameline panel, so I will need to upgrade the service entrance cable and want to use 2/0 THHN copper. The outdoor meter can/box is mounted low, (30" off the ground at bottom edge of can) outside, so if I use the bottom rear 2-inch knockout of the meter can, it will put the hole through the wall below the bottom edge of the new breaker panel by about 8 inches, so I will have to make a vertical 90 upwards turn from hole in wall to bottom knockout of the new panel. I cannot find a 2" close 90 PVC electrical fitting so I'm guessing they don't make one. My question is: how do I make that vertical 90 turn upwards? It will eventually be covered in drywall. Do I need to have the inside copper leads in conduit at all? If I use switch to 4/0 aluminum, do I need conduit inside the wall cavity? thanks in advance!
@TKCL
@TKCL 11 месяцев назад
I can't answer this, your electrica company and building inspection requirements will vary from mine. You need to check with them.
@jeffreyvictor3678
@jeffreyvictor3678 Год назад
Doesn't the new code call for a disconnect after the meter box for FF use in case of emergency?
@TKCL
@TKCL Год назад
It does not here only as long as the meter and main are back to back. FYI my permit was also pulled Dec 2020 before the new electrical xode came out in 2021.
@mike93lx
@mike93lx 2 года назад
If you are running #2 ser to that sub, you can't feed it with a breaker larger than 90a. Also, you do not need anti ox in most situations today. All depends on the wire manufacturer's recommendations. But I don't believe it hurts
@TKCL
@TKCL 2 года назад
My inspector actually asked to see if I did coat it.
@mike93lx
@mike93lx 2 года назад
@@TKCL yeah, but their ask may be based on old info. Either way you did it, so you are good to go. I edited my comment regarding the subpanel feed breaker too, fyi
@TKCL
@TKCL 2 года назад
Actually if you look at the National Electrical Code Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts chart, it has an asterisk by #2 aluminum wire for dwellings and states it allows 100 amps of service. Otherwise you must go by a temperature chart and derate from 100 amps, but there is the allowance if it's a dwelling. Probably because houses don't pull near the current people assume.
@mike93lx
@mike93lx 2 года назад
@@TKCL only is that is the service for the entire dwelling. Otherwise you have to drop to the 75 degree column, which limits it to 90a Not looking to argue, this is just a very active topic on garage journal and I've seen several electricians push it hard, many times, with support
@TKCL
@TKCL 2 года назад
No worries, I like discussing these things. I had no issues with inspection on that, and the likelihood of me ever hitting a full 100 amp load on that sub panel is practically non existent.
@diyoregonnowtexas9202
@diyoregonnowtexas9202 Год назад
I want to learn how to do this, but you said you've never done this before,lol.
@TKCL
@TKCL Год назад
Doesn't stop me from learning and trying. I passed all inspections with only three minor redos.
@seymourscagnetti1413
@seymourscagnetti1413 Год назад
Nice.
@williamhustonrn6160
@williamhustonrn6160 2 года назад
I am not sure if you have the budget for this, but before you do your insulation on the inside, reach out to an aerobarrier contractor and get a quote on it for your area. I had a guy from Tampa come out and do our contractor built 7 year old house and he charged me just under $2/sqft. It was worth every penny, because we dropped our electrical bill by over 50% due to how many leaks were present in the fairly new house. We went from paying almost $200/month in electric to now our bill is typically right around $90-100. Last month we paid $94 and we keep our hvac on 74F.
@TKCL
@TKCL 2 года назад
I won't have time or the budget, but I feel comfortable on how well I've sealed the house. Then add 5 inches of spray foam on top of that.... I should be good.
@TKCL
@TKCL 2 года назад
I'm really hoping after all I'm paying for spray insulation that I have electric bills close to yours.
@cm44-opo
@cm44-opo 2 года назад
Andrew, I hope you saved gabs of money doing all this electrical work yourself. It looks like a very complicated system. Nice job!
@TKCL
@TKCL 2 года назад
Im sure I saved money.... Not time lol
@jeffbecraft7174
@jeffbecraft7174 Год назад
You did a great job. Saved $3k
@balrog006
@balrog006 Год назад
If he did all of his rough in electrical and the meter install, he saved a lot more than $3k on that house.
@TKCL
@TKCL Год назад
Agreed!
@mfd4505
@mfd4505 2 года назад
Bushing on the sub feed cable connector?
@TKCL
@TKCL 2 года назад
That's because it originally had conduit, hard to seal a cable clamp.
@TheFamilyFarmHomestead
@TheFamilyFarmHomestead 2 года назад
LUCKY. We aren't aloud to use Aluminum wire here.
@TKCL
@TKCL 2 года назад
That's all you can find in larger sizes around here
@jfromtn7410
@jfromtn7410 Год назад
so you used a ditch witch to trench the conduit for the 3 inch pvc? this is my plan fir my garage
@TKCL
@TKCL Год назад
We run 2.5 inch here. Yes I rented a ditch witch, totally worth the money.
@TKCL
@TKCL Год назад
Here is the video ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-nFOhHkVBIyM.html
@jfromtn7410
@jfromtn7410 Год назад
oh great thanks! didn't see that video
@mattuk180586
@mattuk180586 Год назад
So you didn’t have to have an outside disconnect for the meter base?
@TKCL
@TKCL Год назад
You don't here as long as the meter base and main panel are back to back. If the main panel is elsewhere and a run of wire goes through the house, a disconnect must be used.
@mattuk180586
@mattuk180586 Год назад
@@TKCL okay. I believe where I’m at you still have to have a disconnect outside and those are hard to come by right now. Thanks for the information. Great video.
@mikemiller5139
@mikemiller5139 2 года назад
👍🎯
@michaelmancini4898
@michaelmancini4898 2 года назад
The grounding rod shall not be less than 8 feet in length and must be free of nonconductive coatings, such as paint or enamel
@johndavies2949
@johndavies2949 4 месяца назад
How come you don't use a meter -main combo outside? So power can be turned off in sn emergency siuation. Doesn't your inspector care? What about fire marshall? Did you take out a permit?
@TKCL
@TKCL 4 месяца назад
You apparently don't know the full code. If placing a meter and main back to back a disconnect it NOT required here. If placing apart a disconnect is required. Fully inspected, passed code ect. Your fire department should be trained to pull a meter as a means of disconnect in an emergency, if not, they don't know what they are doing.
@roberthermsen724
@roberthermsen724 2 года назад
This is probably a crazy question. But what would happen if you decided to build your house way out in the country like you are and you never get the inspection like your supposed to.
@TKCL
@TKCL 2 года назад
Sadly we live in a different world now, the tax collectors office actually reviews satellite imagery to see if any new structures pop up. They also randomly show up unannounced on property too. Makes me wonder how legal this is.
@keithharrington8715
@keithharrington8715 Год назад
Expect your electric company to call and check. The permit office is only a phone call away and with the new meters, power can be turned off from their office.
@stuartkorte1642
@stuartkorte1642 11 месяцев назад
⁠@@TKCLmy office (DOT) is the one that collects the aerials that go to the FDOR and property appraisers. Most countries are on a 3 yr cycle. I’m sure there’s a law that now says they can come on your property. I know property appraisers will come out and measure structures and such.
@paulajones9956
@paulajones9956 2 года назад
2nd YAAAY
@Zeppy007
@Zeppy007 2 года назад
1st in the house 😃
@TKCL
@TKCL 2 года назад
You win! 😁
@dd6892
@dd6892 2 года назад
You forgot the slip joint
@5150cash
@5150cash 2 года назад
Dang this is more of a teaser than your community update 😣😣😣😣 🤞🏽🤞🏽🤞🏽🤞🏽🤞🏽
@TKCL
@TKCL 2 года назад
Well oops!
@PavanKumar-ok6hi
@PavanKumar-ok6hi 2 года назад
Hi grateful job from india iam a electricion
@TKCL
@TKCL 2 года назад
Thank you for watching
@tonysicuro3491
@tonysicuro3491 2 года назад
Have you checked out Wago connectors?
@TKCL
@TKCL 2 года назад
No I'm not familiar with them
@tonysicuro3491
@tonysicuro3491 2 года назад
@@TKCL Would have made things a lot easier. Check Amazon
@tonysicuro3491
@tonysicuro3491 2 года назад
ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-AWiyreFFt-Q.html
@gussoefje6430
@gussoefje6430 2 года назад
I would never recommend just buried wire without conduit. To many animals that can chew it then you have to replace it all
@ShaneZettelmier
@ShaneZettelmier 2 года назад
Grounding codes are weird come out you think they’d be pretty standard, and California people used to ground to water pipes, and it wasn’t uncommon to zap yourself a little bit under running water if you grounded with the other hand. The sinks used to be made of iron coated with ceramic, and old sinks might have chips, a friend had a couple chips in his sink and if you would touch that in the water you’d get a little zap. It’s weird because California has pretty hefty regulations because of earthquake code but they didn’t used to be that picky about grounding I guess. 😂
@TKCL
@TKCL 2 года назад
Yikes 😳
@ShaneZettelmier
@ShaneZettelmier 2 года назад
@@TKCL Don’t worry, manufactures are too cheap do use metal in tubs or bathroom sinks anymore. 😂😂
@TKCL
@TKCL 2 года назад
Lol
@chickenman247
@chickenman247 2 года назад
Your mention of drywalling soon reminded me of a Matt Risinger video from a while back. Anything to prevent pest problems later since your framing is currently exposed. ru-vid.com/video/%D0%B2%D0%B8%D0%B4%D0%B5%D0%BE-LIvPla-07fo.html
@TKCL
@TKCL 2 года назад
Lol your going to like a upcoming episode, I've had that product in my shop ready to go for a few months now. 😉
@Pbell
@Pbell 2 года назад
That Data panel is too close to the electrical panel both covers will not fit without overlapping, and inspector won’t like that on final
@TKCL
@TKCL 2 года назад
Wrong, already covered this in another episodes comments. I have had both panels covers installed with no clearance issue. It's close, but they do not overlap.
@townsend96
@townsend96 2 года назад
You need a day off.. go fishing. Take a nap. 👍
@TKCL
@TKCL 2 года назад
Tell me about it
@mattboutonnyc
@mattboutonnyc 12 дней назад
WRONG >>>concentric knock out... must use bonding bushing MIGB type
@TKCL
@TKCL 12 дней назад
Never once seen a bonding bushing used here on any service to home or shop. Had to look it up.
@mattboutonnyc
@mattboutonnyc 11 дней назад
@@TKCL NEC Section 250.92
@TKCL
@TKCL 11 дней назад
In that same section, this seems like a no. "Because the service neutral conductor provides the effective ground-fault current path to the power supply [250.24(C)], you don’t have to install an equipment grounding conductor within PVC conduit containing service-entrance conductors [250.142(A)(1) and 352.60 Ex 2] (Fig. 2)."
@TKCL
@TKCL 11 дней назад
Isn't the neutral/grounding bar already connected to the metal entrance enclosure? That's then the conductor that connects to the main panel and house ground. I am also using PVC conduit.
@mattboutonnyc
@mattboutonnyc 11 дней назад
Concentric and Eccentric Knockouts: Which Need Grounding Bushings? Sparky Channel 218K subscribers Subscribe your correct....
@user-lp5oc4ne7s
@user-lp5oc4ne7s 11 месяцев назад
Hand Pounding A Grounding Rod.... really? Didn't the international code change back in 2005 or so to require new foundations to include a rebar grounding rod? During the pre-pour inspection, the building inspector makes sure that a stub of rebar is extended up above the top of the foundation for the Ufer ground. E3608.1.2 Concrete-encased electrode. A concrete-encased electrode consisting of at least 20 feet (6096 mm) of either of the following shall be considered as a grounding electrode: 1.One or more bare or zinc galvanized or other electrically conductive coated steel reinforcing bars or rods not less than 1/2 inch (13 mm) in diameter, installed in one continuous 20-foot (6096 mm) length, or if in multiple pieces connected together by the usual steel tie wires, exothermic welding, welding, or other effective means to create a 20-foot (6096 mm) or greater length. 2.A bare copper conductor not smaller than 4 AWG. Metallic components shall be encased by at least 2 inches (51 mm) of concrete and shall be located horizontally within that portion of a concrete foundation or footing that is in direct contact with the earth or within vertical foundations or structural components or members that are in direct contact with the earth. Where multiple concrete-encased electrodes are present at a building or structure, only one shall be required to be bonded into the grounding electrode system. [250.52(A)(3)] ❖ Encasing an electrode in concrete must be done, of course, before the concrete is placed for the footings. The 20 feet (6096 mm) of size 4-AWG bare copper conductor is run in the forms close to the bottom of the footing before the concrete is placed. Enough conductor is left extending out of the footing to be run to the service equipment without a splice. At the point where the copper conductor exits the concrete, it could be broken off by being bent back and forth several times before and during construction. To help protect this conductor, a nonmetallic conduit around the conductor where it leaves the footing would be helpful. In some installations, the end of a horizontal reinforcing bar in the concrete is bent upward so as to create an above-ground exposed connection point for a grounding electrode conductor. In other cases, concrete contractors have been known to provide a short piece of steel-reinforcing rod bent at a 90-degree (1.57 rad) angle and tie-wire it to a footing reinforcing bar for the purpose of providing a stub out for the electrician to connect to. The code does not appear to address these practices and it is the author′s opinion that the code does not anticipate that connections will be made that are solely dependent upon a scrap of rebar that is scabbed (tie-wired) onto the functional rebar. It is noted, however, that the code does allow multiple pieces of rebar to be tied together to create a 20-foot (6096 mm) or longer electrode, assuming that such pieces are placed horizontally in the concrete as required by this section. The best conducting path will likely be achieved where the grounding electrode conductor connects directly to the functional reinforcing steel. The code does not assume that the reinforcing steel bars are present because they are required as part of the structural design, although that is typically why they would be present. Reinforcing bars could be installed for the sole purpose of creating an electrode.
@TKCL
@TKCL 11 месяцев назад
So how does this pass a crawl space foundation with zero concrete? The code here (fully inspected) requires two ground rods spaced a minimum of 6ft apart for any main service panel.
@jareddory2155
@jareddory2155 2 года назад
12:15 CRINGE! You left no excess
@TKCL
@TKCL 2 года назад
No excess what? Ground? That's a very easy fix
@jareddory2155
@jareddory2155 2 года назад
@@TKCL networking guy here, we leave excess everything, I would have looped the feed to the panel around the meter, and up into the lugs to leave “service loop” I realize that stuff is expensive
@TKCL
@TKCL 2 года назад
I've left everything in excess in my boxes and panels. I will however leave zero excess in a meter box with exposed 200 amps of 240 volt lugs everywhere. That's asking for trouble in my opinion, a meter box has way too much exposed metal conductors for my comfort.
@ieatmonkeys9543
@ieatmonkeys9543 Год назад
Alright man I’m three days in and I’ve noticed a bunch you did wrong
@teveler
@teveler 2 года назад
Well done sir... However you will never make it as a professional electrician. You failed the first step, you cleaned up after yourself. ( just a joke that people in the trades get)
@TKCL
@TKCL 2 года назад
Oh lord, here come the comments 🍿😳
@earlcavenaugh6459
@earlcavenaugh6459 2 года назад
Great job Andrew. No matter what the inspector found you have learned a lot and taught us a lot.
@TKCL
@TKCL 2 года назад
Thank you , it's been a heck of a learning experience.
Далее
Biggest house inspections thus far! #458
15:32
Просмотров 14 тыс.
МАРИЯ ГОЛУБКИНА О БАБУШКЕ #shorts
00:43
D3 BMW XM LABEL Король.
31:52
Просмотров 797 тыс.
How to Install and Wire a Sub Panel
35:23
Просмотров 1,3 млн
Full 200 AMP Electrical Service Upgrade Install
37:01
Просмотров 170 тыс.
Why Neutrals & Grounds are Connected in a Main Panel
20:13
How I wire a panel (an in-depth tutorial)
9:57
Просмотров 1,4 млн
How to build a Meter Loop for new electric service
2:16
МАРИЯ ГОЛУБКИНА О БАБУШКЕ #shorts
00:43