AC Not Cooling Correctly 

The HVAC Hacker
Подписаться 32 тыс.
Просмотров 16 тыс.
50% 1

I am on a no cooling service call where the customer complains about an increase in the electric bill. I start testing the system and find the system pressures are low. Therefore I do a leak search and find out the evaporator coil is leaking. I then recharge the system to get it to operate until I can return with a new coil.

Опубликовано:

 

5 окт 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 104   
@Jon-hx7pe
@Jon-hx7pe 5 лет назад
1980s - early 90s: Spend 2 grand or less on a condenser and air handler, electricity under 5 cents per kwh, unit lasts 30 years before springing a leak. only contactor and capacitors replaced. Dehumidified great with a standard psc blower set to high speed. 2016: Spend 10+ grand on a super-high seer proprietary system, electricity 15 to 20 cents per kwh. Needs low blower speed dehumidify feature to keep house comfortable because such a large evap coil is needed to get the SEER rating and it runs 45+ F sst instead of 35 to 40. Coil springs leak in 3 years, angry customer pays labor and refrigerant. A week after 10 year warranty ends, outdoor unit inverter circuit board goes bad, costs $1000 before markup. Unit not worth repair because all the other proprietary parts are ready to go. So much for progress.
@thehvachacker
@thehvachacker 5 лет назад
More like 15k it’s why I keep my customers older units running until they start leaking or a major repair comes up
@albertastorms
@albertastorms 5 лет назад
This is why I will only install single stage and single speed hvac units in my house! The way we used to heat and cool for 60 years was fine, no need to have more than one stage of heating and cooling! If it is too expensive to pay bills, move to a new town and city where it is a lower cost of living!
@Jon-hx7pe
@Jon-hx7pe 5 лет назад
staging is for comfort. i think 2-stage heat (furnace) is worth it and the repair costs aren't much more than for single as long as it has a blower motor that can be replaced with a non-proprietary one (there are generic x13 replacements) and the inducer isn't ecm. The super high end variable capacity stuff looks like way more $$$$ to fix.
@thehvachacker
@thehvachacker 5 лет назад
Jon this is the high end variable capacity modulating compressors with condenser fan motors that modulate to liquid line temps. Lots of money to repair once the 10 year warranty is up.
@thehvachacker
@thehvachacker 5 лет назад
Mesedrew that’s why for my dad I installed a 14 seer 80% furnace. Parts are built to last and inexpensive to replace. I can easily swap any parts with after market instead of you supplier telling me the only communication board for my unit is in California and I live in Jersey
@edspilman9628
@edspilman9628 5 лет назад
Sorry but your camera work on this video makes it almost unwatchable.
@watermanone7567
@watermanone7567 5 лет назад
Nice job: I can't understand where the damn building inspectors are when they allow those kinds of installations that ultimately cost the home owners huge money to fix something that normally takes about 4hrs. Thanks for the video.
@thehvachacker
@thehvachacker 5 лет назад
I wish this install was failed. I rather pull a coil. Instead of disconnecting a hung air handler, move it 2 feet, to be able pull the coil with almost no room to work
@walkingfreak
@walkingfreak 5 лет назад
this is why i lean more towards food and beverage refrigeration more than anything. But even the superheat looks high for that kind of system and the suction line temp unless it wasn't running full throttle. Even pouring down rain subcool should be in range.
@thehvachacker
@thehvachacker 5 лет назад
I ran out of 410a. The subcooling should be closer in range with the rain. Yet with no more gas it’s where it stayed I got the system operating. I shifted the system into test mode which ramps the compressor to 100%. These systems can run 14-25 degree superheat and still produce a 20 degree split. I was nowhere near the 12 degrees of subcooling
@jburr36
@jburr36 5 лет назад
highest power bill I had this summer was $65 and that was because I ran my freeze dryer every day for a few weeks. Those 7 cfm 2 stage vacuum pumps eat a lot of power when ran for 24-36 hours straight
@davyime1368
@davyime1368 5 лет назад
That's a real nice hole in the metal plate for your hoses to check the charge on that unit. It's almost like you need smart probes :)
@thehvachacker
@thehvachacker 5 лет назад
I no longer have my old testo 550 I should get an adapter to work the hose out the condenser. Yet couldn’t get the proper sweep
@ronaldzeigler9057
@ronaldzeigler9057 5 лет назад
Si know that no problem thanks for responding
@workinprogress4579
@workinprogress4579 5 лет назад
Sounds like a nightmare coil. Nice work
@thehvachacker
@thehvachacker 5 лет назад
That it was
@fredflintstone8048
@fredflintstone8048 5 лет назад
Nice job. Thanks for sharing.
@thehvachacker
@thehvachacker 5 лет назад
Thanks Fred
@johntilson2535
@johntilson2535 5 лет назад
sounds like it started to rain while you were in the attic!
@thehvachacker
@thehvachacker 5 лет назад
Yes it was pouring off and on during this job. First time I checked refrigerant pressures from my truck
@JuanTodoli
@JuanTodoli 5 лет назад
Good one Bill. Excelent job. 👍
@thehvachacker
@thehvachacker 5 лет назад
Thanks the video part was easy compared to changing the coil that I didn't record
@JuanTodoli
@JuanTodoli 5 лет назад
@@thehvachacker I can imagine.
@abcdefghi2175
@abcdefghi2175 4 года назад
if you live in the south you dont hear the locust at all yall
@sknight0391
@sknight0391 5 лет назад
Lennox units work great....When they have refrigerant in them. Which isn't very often. I wish I would have documented every leaking Lennox Coil I've found over the years. Although I did work on a Lennox xp17 yesterday, the one with the Emerson climate technologies compressor with the bell-shaped hard plastic cover over it, and it was fine. It's been in about eight or nine years now with no refrigerant added. But Lennox has definitely got some major coil issues.
@watermanone7567
@watermanone7567 5 лет назад
I agree, customers pay for the big name units with all the bells and whistles and usually the cheap units work just as well if not better. I had a customer that had a very old system that was working great and decided to replace it when they remodeled their house, bottom line is the new unit is nothing but trouble, guess what name it is? with leaking coils.
@codywiggins9387
@codywiggins9387 5 лет назад
They have improved quite considerably with their new evap and condenser coil design. Labeled as "Quantum Coils". We've seen much better success out of them.
@neutrodyne
@neutrodyne 5 лет назад
When working on a Lennox unit with a bad coil do you replace it with a different brand coil? If you do what brand coil do you replace the Lennox coil with?
@sknight0391
@sknight0391 5 лет назад
@@neutrodyne Nope, you go back with another Lennox.
@watermanone7567
@watermanone7567 5 лет назад
I used a local named unit, usually made by Carrier but many others use the units with their own names on the. Temp Star comes to mind for one of them.
@superiorcomfortheatingairl3373
If the owner complains again about the electric bill, tell him to purchase the Lennox solar panel kit, lol
@thehvachacker
@thehvachacker 5 лет назад
He was running the system at 70 degrees all summer with it not cooling. I don't care how hi efficient that system is. Without refrigerant that compressor was ramped at 100% all summer. I have yet to see a solar kit
@Chris_In_Texas
@Chris_In_Texas 5 лет назад
Someone needs to wrap the condensate lines in pipe insulation. They are drooling all over.
@archiedarwin7763
@archiedarwin7763 3 года назад
a tip : you can watch movies on Flixzone. Been using them for watching a lot of movies recently.
@zavierlevi3529
@zavierlevi3529 3 года назад
@Archie Darwin yup, I have been watching on Flixzone for months myself :D
@Eddy63
@Eddy63 5 лет назад
Another nice fix Hackster ...
@thehvachacker
@thehvachacker 5 лет назад
Thanks Eddy
@jamesjohnson9050
@jamesjohnson9050 3 года назад
That’s why I don’t sale Lennox there inside coils r junk
@chriseh09
@chriseh09 5 лет назад
Do you profile your systems or just use the Job Links as gauges? I really appreciate the time and effort you put into a service call. In todays world most companies want a tech to run 8-10 calls a day and it's hard for them to put the work in as you do...great job!!!
@thehvachacker
@thehvachacker 5 лет назад
I profile my systems sometimes. I been creating projects when commissioning new equipment. Yet many times while troubleshooting I just use them like gauges.
@ronaldzeigler9057
@ronaldzeigler9057 5 лет назад
I just saw a add on I did not like but no problem I like you smart
@thehvachacker
@thehvachacker 5 лет назад
I have no control on the adds. I wish i could pick and choose what adds they can place on my vids
@donnierobertson3088
@donnierobertson3088 5 лет назад
Nice job
@dmitrinachumovhvacapplianc1597
Good job
@sknight0391
@sknight0391 5 лет назад
Wouldn't it be funny if the measure quick app said the system problem was... "You're working on a Lennox and it most likely has a leak at the indoor coil." 🤣🤣🤣🤣🤣🤣🤣🤣🤣🤣🤣
@hozerhvac4406
@hozerhvac4406 5 лет назад
Xc25 and this is the type of shit customers have to deal with. Typical lennox. Leaking coils weekly. Unreal
@sknight0391
@sknight0391 5 лет назад
@@hozerhvac4406 yeah it is almost an every-week kind of thing with us. Haven't seen enough of the aluminum indoor calls to give an opinion on them. Although one of our guys has already found a leak on an aluminum. We're dealing with rain and Bosch equipment now and both have been pretty good so far. Lennox has cost homeowners and dealers millions of dollars with this leaky coil issue. that's always been my biggest gripe with this industry. There are no real standards or regulations to protect people against this kind of stuff.
@thehvachacker
@thehvachacker 5 лет назад
Is it really just a lennox problem? Just sucks on a very expensive system. I heard carriers also have lots of leaky coils. Yet where i work installs thousand plus units a year so I will definitely run into leaks
@50KALKILLER
@50KALKILLER 5 лет назад
Did that air filter really have it dated that it was put in 07/18/18?! I'm surprised it didn't ice itself due to low airflow- probably would have if not for the leak. lol
@thehvachacker
@thehvachacker 5 лет назад
Those filters in ac only systems last 2 summers before becoming restrictive. Now the honeywell filters don't usually last one season
@stoddern
@stoddern 5 лет назад
Did you ever find out why your gas detector was flipping out about gas coming up out of the ground all over that street a few weeks back?
@thehvachacker
@thehvachacker 5 лет назад
No i didn't yet it hasn't done that since only going off when i hit a leak.
@nightmareinaction629
@nightmareinaction629 5 лет назад
The HVAC Hacker which video its it ?
@poellot
@poellot 5 лет назад
@@thehvachacker mine will beep much faster when i put it in grass, not enough to set it to alert but very close.
@851995STARGATE
@851995STARGATE 5 лет назад
@@poellot decomposition of methane possibly?
@vernonbaker4674
@vernonbaker4674 4 года назад
0
@Sctronic209
@Sctronic209 5 лет назад
No insulation on the sensing bulb.
@thehvachacker
@thehvachacker 5 лет назад
Never is their insulation on the sensing bulb. The way the coil is designed no air goes across that area so it’s only sensing the suction pipe right past the coil
@tomh6779
@tomh6779 5 лет назад
Hey! I noticed you have one of those Mercedes vans. Any good? You had a ford transit before? Thoughts?
@thehvachacker
@thehvachacker 5 лет назад
It’s a good van doesn’t use much gas as the old Chevy vans 2500 with the nice v8 engines. Yet also lack in acceleration. That’s really not a bad thing carrying all this weight in the truck. I never had a transit yet my company has switched from the sprinters to the transits beginning of 2018. We have had all sort of problems with both. Yet we also have 50+ service vans on the road. I was the last sprinter upgrade. Trading in my 09 dodge sprinter for the 17 Mercedes sprinter. Same truck few dash changes and better turbo. The turbo use to always drop out of my old sprinter. No acceleration or power once that happens. Some of the transits have had transmission issues and engine failures. I would prefer keeping the sprinter cause the taller transit seems too tall. Plus I’m just use to the sprinter
@charleyh8340
@charleyh8340 5 лет назад
You could of swapped just the coil instead of the whole box in that ocasión .
@thehvachacker
@thehvachacker 5 лет назад
The coil was replaced. The air handler had to be uninstalled and moved 22 inches forward to clear a main support in the attic
@hvac97849
@hvac97849 4 года назад
The job was a shit show from the get go. If the Effing manufacturer's would do better quality control, but no. Whip it zip it send it out, let the contractor figure it out.
@renj6531
@renj6531 5 лет назад
I was just about to ask is that rain
@thehvachacker
@thehvachacker 5 лет назад
It was raining off and on the whole job. Part of it I filmed sitting in my truck waiting for it to pass
@edjovi3677
@edjovi3677 5 лет назад
wow looks like a dryer screen lol edbonjovi
@thehvachacker
@thehvachacker 5 лет назад
The coil on the 25 seer unit plugs quickly
@edwinjewell5359
@edwinjewell5359 5 лет назад
These newer Systems S### 80s 90s much much better.
@Spector_NS5_RD
@Spector_NS5_RD 5 лет назад
Don't you love jobs like that? LOL Crushed into the fetal position, for 9 hours, in a hot fiberglass coffin. Just curious Bill, how old was that system? 2012? Has Lennox switched over to all aluminum evaps yet? Great video my dude.
@thehvachacker
@thehvachacker 5 лет назад
Its a 2016 system and yes the new lennox systems have all aluminum coils now. Is the aluminum coil stronger? We will find out. Worst part of the coil swap was my right arm was feeling better no pain. I reinjured it on that job. I don't mind install work or unit swap out. It just sucks when their is no room to work
@edjovi3677
@edjovi3677 5 лет назад
bill hello from the leak master !!!! talk too soon edbonjovi
@thehvachacker
@thehvachacker 5 лет назад
Talk to you soon leak master
@GimmePrize
@GimmePrize 5 лет назад
Great video but wear gloves next time your messing with refrigerant lmao
@samuelmontera7603
@samuelmontera7603 5 лет назад
hello can i have advice coz my aicon is frostying on highside what is this means.
@jakurt9458
@jakurt9458 5 лет назад
Which leak detector is that
@thehvachacker
@thehvachacker 5 лет назад
I use the inficon d-tek had this one since 2006. Been reliable and get me close to the leaks r-22 or 410a
@vogelservices6769
@vogelservices6769 5 лет назад
I hear the locusts in the background, where are you located?
@stoddern
@stoddern 5 лет назад
He's in Mass
@thehvachacker
@thehvachacker 5 лет назад
New Jersey
@vogelservices6769
@vogelservices6769 5 лет назад
I learned my trade in Manhattan, had to come back to a slower pace though. At least that A coil want be so bad.
@thehvachacker
@thehvachacker 5 лет назад
That a-coil sucked to pull. when you see me leak searching there is a support beam going up to the roof rafters. Its supporting 5 different angles joining together. This prevented the coil from just sliding out. I wasn't going to cut it or move it out of the way. Attic was not even 3 foot tall. Had to move air handler 21 inches forward. Supply, and return needed to get disconnected and fitting into eve to disconnect ducts wasn't fun. The coil changeout took 9 hours 2 guys. I wrote it up for 2 small techs and they send me and another big guy to pull this off.
@RenegadechefxMBR
@RenegadechefxMBR 5 лет назад
Did you get your other probe back?
@thehvachacker
@thehvachacker 5 лет назад
No I ordered a new one since i miss the convenience of having two probes. If I get the probe back then I have three. So then I can do suction line, liquid line and discharge line temp at the same time. Yet the customer never called me back and it’s been almost 2 weeks so I doubt they will. It’s a water sourced heat pump self contained in a closet. Not even an outdoor condenser or I would just go to the unit and get it back
@RenegadechefxMBR
@RenegadechefxMBR 5 лет назад
Ahh damn... I’ll keep my fingers crossed for the safe return of your item lol. I did that with my drill the other day...got to my next job an had an oh shit moment
@thehvachacker
@thehvachacker 5 лет назад
The job was end of the day on a Friday and the lady was in a rush to get on the road for labor day weekend. ahhhhhh
@ronaldzeigler9057
@ronaldzeigler9057 5 лет назад
Do not put them on your site
@thehvachacker
@thehvachacker 5 лет назад
May I ask put what on my site?
@ronaldzeigler9057
@ronaldzeigler9057 5 лет назад
This insurance add is all lies
@thehvachacker
@thehvachacker 5 лет назад
What insurance add? I have no control of the adds youtube places on the videos
@mikegolmon8375
@mikegolmon8375 5 лет назад
Pretty unfriendly instillation for some poor ac tech to service the equipment...
Далее
No Heat Service Call T-Stat Satisfied Upon Arrival
36:11
Песня РАСПУТИН на русском!🔥
00:56
Low Refrigerant? Freon Leak? Check This First!
7:02
Просмотров 434 тыс.
Capacitor and Hard Start Myths Busted
28:41
Просмотров 249 тыс.
How to Evacuate an AC system, Full Vacuum Procedure
27:35
All AC Parts and What They Do
33:18
Просмотров 1,7 млн
How to properly charge a system
21:53
Просмотров 99 тыс.
Thermoelectric cooling: it's not great.
32:51
Просмотров 2,4 млн
Explaining Superheat and Subcooling to Your Apprentice!
14:14
Песня РАСПУТИН на русском!🔥
00:56