I arrive at a no heat call. I find the Roof Top Unit inducer running yet cold air coming out of vents. The inducer starts and all safeties closed so the smart valve was lighting the hot surface ignitor. Yet the pilot wasn't lighting. This prevented the gas valve from energizing the main gas valve. I check gas and have gas present at the valve. I find the pilot hood wasn't putting the gas correctly across the Ignitor preventing the pilot from lighting. I bent the pilot hood to get the gas to go across. After this, the heating system would fire the burners off every time.

Опубликовано:

 

25 авг 2024

Поделиться:

Ссылка:

Скачать:

Готовим ссылку...

Добавить в:

Мой плейлист
Посмотреть позже
Комментарии : 150   
@michaelkeudel8770
@michaelkeudel8770 11 месяцев назад
After 5 hours being annoyed with my furnace, new gas valve, new control board, I still had no pilot, nozzle was clogged. Good thing I do my own work, at least I only paid $300 for the parts, but the no pilot was annoying. Watching him made me check my pilot gas, was there, still couldn't light at the nozzle. Took the assembly out, found a small pin, cleaned out the nozzle, hurray, working furnace. Thanks man.
@killswitchtaco8178
@killswitchtaco8178 5 лет назад
Good fix bro, one thing I can never understand is this is the only trade where everyone is perfect and bash all the guys who don't do it "their" way. Support and help the guys around you. Keep up the Good work and ill be watching and reading all the supertechs comments......asshats
@thehvachacker
@thehvachacker 5 лет назад
This was interesting, I wonder if that was the correct hot surface ignitor or if somewhere someone changed it and until the other RTU was shut down a day earlier for bad heat exchanger no one noticed this RTU wasn’t heating? We all need to help each other learn to get better in this trade. If more can do what I can and more my job becomes easier.
@Bryan-Hensley
@Bryan-Hensley 5 лет назад
@@thehvachacker you should delete some of the comments from people who have no subscribers or content. Especially if they are using a fake name that has nothing to do with their channel. I think we have true paid trolls to do nothing but create turmoil.
@JerryLynch2
@JerryLynch2 4 года назад
Amen! SPOT ON! We're all supposed to be brothers and sisters who picked this s*** to make a living.
@mwdub02
@mwdub02 5 лет назад
Keep up the good work bro. Glad to see another rtu repair. Keep’em coming.
@thehvachacker
@thehvachacker 5 лет назад
I get some breakdowns among many of my all day maintances.
@thefred0215
@thefred0215 2 года назад
I thought these were 24v ignitors? How come you were getting only 9v?
@lijoima
@lijoima 3 года назад
Hey hacker! You saved the day for me with the idea of bending the pilot outlet! My parent's 28yo furnace pilot would not light unless you blew slightly at the pilot while it was sparking. I tried this hack and BINGO! Thanks for your vids!
@DONALD1951
@DONALD1951 5 лет назад
Wow...some rude folks watching. He’s doing a good job.
@thehvachacker
@thehvachacker 5 лет назад
I’m use to it
@superiorcomfortheatingairl3373
Treat it like it was a boiler and give it some rough justice💪
@thehvachacker
@thehvachacker 5 лет назад
Here is my only concern. Why did I have to bend the pilot hood so gas would hit the ignitor? How did this thing ever work?
@mikesmart239
@mikesmart239 5 лет назад
Glad to see more videos from you
@thehvachacker
@thehvachacker 5 лет назад
Thanks
@2mehvac59
@2mehvac59 5 лет назад
Good vid bro, ill be tuning in for any new ones. Thanks for taking the time to post. Us hvac junkies need our fix.
@thehvachacker
@thehvachacker 5 лет назад
Thanks this was an interesting experience
@erikcable1755
@erikcable1755 5 лет назад
hackville usa....sweet fix mr. know how it's done...carry on
@doh1976
@doh1976 3 года назад
ima be down in the basement using your hacker methods on my pos furnace in a minute
@jaycurtis3092
@jaycurtis3092 5 лет назад
You ought to looking into buying a set of hypodermic probes for those Molex plugs, makes testing sooo much easier!
@thehvachacker
@thehvachacker 5 лет назад
I have them for back probing moles plugs. They were in my van and not on me. Which slide into the plug so much easier. I keep them and alligator lead adapters in a red pouch.
@3740westmichigan
@3740westmichigan 5 лет назад
One hell of a hack!!!!!!!!!!!!!!!!!!!! love it
@thehvachacker
@thehvachacker 5 лет назад
I do what I can. Just who hacked it before me? How did it ever work if the pilot gas didn’t hit the ignitor.
@3740westmichigan
@3740westmichigan 5 лет назад
right on love all of your vidjas !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
@thehvachacker
@thehvachacker 5 лет назад
Thanks Rip
@rodgraff1782
@rodgraff1782 5 лет назад
Honeywell smart valve system with low voltage HSI. So much more complicated than it had to be. The only thing I disliked worse was the old White Rodgers IID systems with the plug in mercury sensor at the gas valve. Was glad when everyone went to DSI and got rid of the pilot all together. A lot of those smart valves were defective at the plug connectors. We had one smart valve unit where a small beetle would climb into the pilot hood once a week, blocking the gas flow. For some reason the bug was attracted to that pilot. Good job hack.
@thehvachacker
@thehvachacker 5 лет назад
These are interesting yet prefer having separate ignition module and gas valve. Did you kill the beetle to prevent any more callbacks? That had to be tough to figure out unless you found him in the pilot hood
@throttlebottle5906
@throttlebottle5906 5 лет назад
let me guess, stinkbugs
@billy5032
@billy5032 4 года назад
24volts comes out of the gas valve on the orange wire to the main board after main burner ignition to start the timer for blower
@watermanone7567
@watermanone7567 5 лет назад
Great fix, probably someone else was there before you. I have had something like that many times. Thanks for the video's.
@thehvachacker
@thehvachacker 5 лет назад
A day before i was sent on this call the other rtu was shut down with a cracked heat exchanger. Who knows how long this unit was down for. pilot assembly looked kinda new no white powder on the orifice.
@Kustomgadget
@Kustomgadget 2 года назад
I've seen this a couple of times, one just last week. For whatever reason, the ignitors doesn't work up to their full potential sometimes. A new ignitor will glow almost twice as bright and light the pilot every time. Sometimes I use a propane torch or lighter to light the pilot and the burners will work. I have broken the pilot assembly bending them that way. I hate when that happens. lol
@Walterz930
@Walterz930 5 лет назад
Nice video when my on demand water heater pilot stopped working I blow compressed air thought then it worked again it was gummed up
@thehvachacker
@thehvachacker 5 лет назад
Nice fix to get some hot water. The downfall to the on demand hot water heaters is most areas have a high mineral content in the water. This sticks to the inside of the heat exchanger. I hook a pump up and fill a 5 gallon bucket with water and ice machine cleaner and let that rinse through to clean off the mineral. Many issues are also found on the inlet screen which may get restricted.
@drewdude444
@drewdude444 5 лет назад
Love the vids man thank you
@thehvachacker
@thehvachacker 5 лет назад
Thanks, this was an interesting one
@stueygreenberg8989
@stueygreenberg8989 4 года назад
WOW! Takes the pilot port out of gas valve to check for gas. Classic!
@thehvachacker
@thehvachacker 4 года назад
Truck was a few blocks away. I knew I had gas coming out. I blew out the pilot tubing, cleaned orifice and hood which didn’t make the video. I was able to light the pilot with a lighter.
@JerryLynch2
@JerryLynch2 4 года назад
@@thehvachacker Hey, screw'em! People kill me with their systemic cross your t's and dot your I's only concepts. It wasn't like you were in a confined space. You're on a rooftop with a world of ventilation... and you need to know if you have gas...mission accomplished. These new pansies don't know anything about old-school tricks. They're the same ones that piss on themselves if you have to piggyback a capacitor to get by. Good job!
@TheMaster5150
@TheMaster5150 4 года назад
@@JerryLynch2 God forbid you show them how turn that piggyback into a bomb in a pinch. They might take ya seriously...lol
@JerryLynch2
@JerryLynch2 4 года назад
@@TheMaster5150 Loooool! Rolling on the floor.
@throttlebottle5906
@throttlebottle5906 5 лет назад
interesting, thought maybe someone changed the pilot assembly or igniter and just jammed one in that was close, but after watching further, looked like it wasn't pulling and mixing air with the gas on the pilot, seemed to have a big lazy rich flame, and burning something out of it, so probably a bug/spider in the pilot tube above orifice or down inside blocking the air bleed holes. if you have pilot gas flow, the easiest way to confirm some blockage is a long lighter to light it manually. you can sometimes put flame into the air bleed holes and get what in there burnt out or clear it by blasting high pressure air through the side air holes or down the tube unhooked from gas valve. of course the igniter can get broken pretty easy playing with hoses and air, who hasn't broken them before fiddling around or dropping them, I've broken two in a row before on a rather sick and clumsy day :(
@thehvachacker
@thehvachacker 5 лет назад
I deleted the part where i removed the pilot tubing and checked to make sure nothing was blocking it. Pilot orifice and pilot hood looked clean no white dust powder build up and nothing restricted. The first light up I had the pilot gas cranked al the way.
@throttlebottle5906
@throttlebottle5906 5 лет назад
hmm, maybe the gas valve is starting to get stupid or just a large load of air mixed in the gas lines, because from what I recall on those units, the flame should have been nearly double what it was when you had it lit outside the unit. the yellowish could have just been rust when it first lit then, but who knows. I also assumed that was an air-bleed style, but I don't recall them 100%.
@kdmq
@kdmq 5 лет назад
Nice job only question is who put the unit back on the roof after Mario and Luigi threw it off the bridge?
@thehvachacker
@thehvachacker 5 лет назад
It ate a mushroom and feel into a tunnel that warped it back onto the roof
@jeffgrant6914
@jeffgrant6914 5 лет назад
good video man
@thehvachacker
@thehvachacker 5 лет назад
Thanks Jeff
@rschramm2088
@rschramm2088 5 лет назад
in the video looks like main gas valve is in the off position ???
@vicvillalta644
@vicvillalta644 5 лет назад
“”THE JERSEY HACKER DOES IT AGAIN”” A very talented hacker at that but can’t sing for shit. You crack me up dude. Sometimes you have to let the hacker out. Hey they have heat right so haters can suck the balloon knot.
@thehvachacker
@thehvachacker 5 лет назад
Just having fun working
@jeffcoolhd
@jeffcoolhd 5 лет назад
There goes another satisfied customer. The hacker. Peace brother
@thehvachacker
@thehvachacker 5 лет назад
I do my best for my customers
@gregmccarthy6011
@gregmccarthy6011 5 лет назад
was pilot orifice plugged or did you just bend hood, I saw very small allen put back
@thehvachacker
@thehvachacker 5 лет назад
I had to bend the hood. Never had to do that before. Yet the gas wasn’t hitting the hot sureface ignitor.
@Heavy_metal_rulez
@Heavy_metal_rulez 5 лет назад
Hacker huh? I think not! Now that P-trap zip tied to the gas line might be in the hack category
@thehvachacker
@thehvachacker 5 лет назад
Someone somewhere hacked this system.
@edjovi3677
@edjovi3677 5 лет назад
plugged tube eddie leak master
@shadowbanned69
@shadowbanned69 5 лет назад
Did that unit have a pilot???? And a glow igniter???? I know those rtu's either had spark ignirers or glow ignites but no pilot tubes...wow I've never seen that model
@sknight0391
@sknight0391 5 лет назад
Jesse that's how smart valves operate. Black and white wires supply 24 volts to the valve, blue wire sends voltage to the igniter which lights a pilot flame and then the main burners like off of that. Then power goes through the orange wire to the main control board to turn the blower on. 👍
@thehvachacker
@thehvachacker 5 лет назад
Yea this is the infamous smart valve. The gas valve sends power to the ignitor as long as safeties are closed. They built the ignition module into the gas valve. I just want to know why did I have to bend the pilot hood so the gas for the pilot would hit the hot surface ignitor. This style gas valve was around for awhile. And many do not like it.
@shadowbanned69
@shadowbanned69 5 лет назад
@@thehvachacker yea I see why...looks like a pain
@SombraLocs
@SombraLocs 5 лет назад
The HVAC Hacker is it all 24 volts?
@thehvachacker
@thehvachacker 5 лет назад
Yes the valve is all 24 volts
@subsonic3633
@subsonic3633 3 года назад
oh so your the guy that warps the pilot nut so i can't get my wrench on it lol. good eye on that pilot tho.
@DONALD1951
@DONALD1951 5 лет назад
Check for 24 volts at the gas valve. If there is then. the valve may be bad. Pilot. Hits flame sensor. Board senses signal from the sensor and sends 24 volts to the valve.
@thehvachacker
@thehvachacker 5 лет назад
Had 24 volts to the board and 24v through all the safeties to energize the ignitor part of the gas valve. Gas just wasn’t going across ignitor
@edjovi3677
@edjovi3677 5 лет назад
love it !!!!
@hvac01453
@hvac01453 5 лет назад
the minute you said 22Volts, I knew the transformer wasn't wired properly. I saw the taps were on the two outside taps, WRONG!
@garyoconnordbaairrepair7775
@garyoconnordbaairrepair7775 5 лет назад
I had to see why a package unit did not work today. The unit I checked out today looked exactly like this unit. I had a bad control board, fuse to the transformer and T3 connector.
@thehvachacker
@thehvachacker 5 лет назад
Do you think the t3 connected caused all the problems?
@garyoconnordbaairrepair7775
@garyoconnordbaairrepair7775 5 лет назад
The HVAC Hacker possibility.
@shadowbanned69
@shadowbanned69 5 лет назад
Ok cool thanks, didnt know that. Only seen pilots and auto starters without pilots
@thehvachacker
@thehvachacker 5 лет назад
Usually around here we have standing pilots, spark ignition pilots which a spark ignites a pilot flame or gas off burner straight, then hot surface ignitor. Until we get to this infamous smart valve which uses the hot surface ignitor to light a pilot flame so the flame sensor sends a signal to gas valve to open main burner. This is an expensive overkill gas valve/ ignition system
@TedCookHVAC
@TedCookHVAC 5 лет назад
@@thehvachacker I hate smart valve systems.
@FireandFrostHVAC
@FireandFrostHVAC 5 лет назад
Good video. I wonder if a previous tech installed the wrong igniter? Or maybe the igniter was just worn out?
@thehvachacker
@thehvachacker 5 лет назад
I think someone changed the ignitor or the pilot hood. Not sure which yet they never realized this unit wasn’t working until the other unit on this roof was shut off 1 day earlier due to a cracked heat exchanger.
@jimwainwright5725
@jimwainwright5725 5 лет назад
did you check for spider in pilot
@Eddy63
@Eddy63 5 лет назад
Another save by the Hackster ...Lol ... Good vid Hack ... I think your a great singer and actor ... But I drink a lot ... So ...
@thehvachacker
@thehvachacker 5 лет назад
Hahaaa this is was an interesting call
@HVACRDUDE
@HVACRDUDE 5 лет назад
Killed me bro 😂🤣😂🤣love your channel
@thehvachacker
@thehvachacker 5 лет назад
Thanks, I just have fun fixing whatever I run into
@justinklrjms
@justinklrjms 5 лет назад
Spider in the pilot?........on thr boilers I work on with a pilot spiders love pilot and burner orifices.....go figure..... ...Love when they leave when you start taking it apart....
@thehvachacker
@thehvachacker 5 лет назад
No, I forgot to include the part of the video where I puller pilot tubing blew it out and checked orifice yet orifice looked brand new no white dust on it. put it back and still no ignition. Didn't want to bore everyone watching the HSI glow and go out numerous amounts of time. Yet I regret not including that since many are wondering if something was blocking the orifice or pilot hood.
@marcusdarnell3348
@marcusdarnell3348 3 года назад
Great video! When u r replacing a gas valve couldn't you count the number of turns as you are taking it off to get the same orientation
@jth1699
@jth1699 4 года назад
Where did you get that cute 90* angle driver for your drill??? I'd like one
@thehvachacker
@thehvachacker 4 года назад
Home Depot sells it. The one I’m using here has been discontinued. I like the newer version of this tool. It’s easier to hold and made for an impact unlike the one in the video
@thefred0215
@thefred0215 2 года назад
What camera do you use btw?
@frankevans588
@frankevans588 5 лет назад
ANOTHER SUCCESSFUL HACK!!!!
@thehvachacker
@thehvachacker 5 лет назад
Thanks frank
@jeffgrant6914
@jeffgrant6914 5 лет назад
Nice trouble shooting video / repair
@thehvachacker
@thehvachacker 5 лет назад
Thanks Jeff
@petesingh292
@petesingh292 3 года назад
Hey hacker , you got good singing voice lol
@royamberg9177
@royamberg9177 5 лет назад
The shit I guy runs into when you go to the job site. How did it get bent so far off
@thehvachacker
@thehvachacker 5 лет назад
I want to know how did this thing ever work?
@royamberg9177
@royamberg9177 5 лет назад
@@thehvachacker it didn't that's why you got the call. Gas valve looks new
@hvacr3194
@hvacr3194 5 лет назад
화질이 엄청 좋네요 고프로인가~
@rodgraff1782
@rodgraff1782 5 лет назад
Found a different beetle in the pilot hood three times, already dead. Not our fault, had to charge them
@adrianwilson7536
@adrianwilson7536 5 лет назад
I would have checked for small leak bypassing thru pilot, carrion insects are. Attracted to the chemicals added to gas
@TedCookHVAC
@TedCookHVAC 5 лет назад
Keep your day job dude !!!
@thehvachacker
@thehvachacker 5 лет назад
Always keep the day job, I suck at signing so I will just keep playing with broken systems. Good advise ted when does the first episode come out.
@TedCookHVAC
@TedCookHVAC 5 лет назад
@@thehvachacker I am pushing the producer for the end of this month... I had a hard time getting enough footage out of him for that little teaser/trailer that is out.
@md929
@md929 4 года назад
This hacker hacked it so he can hack it. Now that's a hacker!
@curiosity2314
@curiosity2314 5 лет назад
I'm in another biz and might be considered a hacker also and not a parts changer and get to what is causing the issue. Seems although in this biz checking efficiency on the way out would be part of the game? I know it is not you but the trade in general like mine, get in and get out. A lot of waste in not checking gas pressure or other on the way out. I gave you a thumbs up for getting it working but my mind says other things needed to be done to be correct.
@DONALD1951
@DONALD1951 5 лет назад
Curiosity the efficiency is preset.
@thehvachacker
@thehvachacker 5 лет назад
If my truck wasn’t parked 2 blocked I would of checked gas pressures. The other RTU on this roof was just shut down a day earlier for having a cracked heat exchanger. This system most likely never was used until the carrier on this roof was shit down. How else could it have been operating with this pilot set up?
@curiosity2314
@curiosity2314 5 лет назад
@@thehvachacker Yes agreed, wasn't getting on you just something I noticed. They have heat and that is what counts, be good to setup a revisit to go over things. Something I would do in my biz. Always respect..
@DONALD1951
@DONALD1951 5 лет назад
The HVAC Hacker serviced many years. Gas pressure is rarely a problem. It’s usually a problem with the pilot or a control. Make sure the gas to the burners is off when you light a pilot outside the burner. You may have. Just a reminder.
@thehvachacker
@thehvachacker 5 лет назад
Donald I would of shut gas to burner off yet then couldn’t test the pilot assembly. This valve set up doesn’t allow to shut the main off and leave the gas on or does it? I put it on my notes to test when replacing the heat exchanger on other RTU
@ask4george1
@ask4george1 5 лет назад
So your not going to set that pilot light up correctly with a manometer, hack. It's not the hood, it was the pilot tube plugged with a spider web. I use a bike cable. It's flexible, run it in the tube and clear out the spider web.
@thehvachacker
@thehvachacker 5 лет назад
It was the hood I had the pilot tubing out and apart. Didn’t change anything I thought I hit record but missed filming that part. Gas was coming out the whole time just wasn’t aimed to hit ignitor. I run into plugged pilots all the time
@notanewbie1718
@notanewbie1718 5 лет назад
Interesting video. The audio is muffled making it hard to understand what you are saying.
@thehvachacker
@thehvachacker 5 лет назад
Could be the wind
@timothycarey2460
@timothycarey2460 3 года назад
Did they pay the gas bill
@williegillie5712
@williegillie5712 5 лет назад
Don’t ya hate working on something someone else that doesn’t know what they were doing was working on?
@thehvachacker
@thehvachacker 5 лет назад
Yes just doesn’t make sense how this ignition system ever fired.
@clintglasgow5633
@clintglasgow5633 5 лет назад
👍
@thehvachacker
@thehvachacker 5 лет назад
👍
@TheLOD2010
@TheLOD2010 5 лет назад
Uff. What a inefficient Burner. No isolation nothing. And I think no Euro 6 exhaust. Some times it is crazy to see what kind of standards other countrys have.
@Bryan-Hensley
@Bryan-Hensley 5 лет назад
For some reason commercial units had virtually no insulation back in those days. I've had to put insulation around the outside of a gas furnace in an attic area because they kept the store around 68 F in the summer. the furnace would sweat and kill the electronics.
@thehvachacker
@thehvachacker 5 лет назад
The lack of insulation causes all the rust inside this unit from condensation. What is euro 6 insulation?
@TheLOD2010
@TheLOD2010 5 лет назад
@@thehvachacker Euro 6 means the exhaust standard for the EU. All heater have to match them or they will be shut down. This also applies to wood burning heaters.
@orderofthegreyjedi
@orderofthegreyjedi 3 года назад
smart valves are not to smart lol, glad they did away with them but are they costly to replace.
@erikcable1755
@erikcable1755 5 лет назад
PS..all you need is a 5 gallon bucket chair...
@thehvachacker
@thehvachacker 5 лет назад
I do instead of kneeling down always. I have a tailgate chair in my truck for when I am doing generator work.
@ks7612
@ks7612 5 лет назад
Holy shit more like HVAC GOD lol
@thehvachacker
@thehvachacker 5 лет назад
No I am just an average tech where I work
@jimk.8783
@jimk.8783 Год назад
If you're getting pilot gas at the valve. You pilot is clogged. clean the pilot.
@proluxelectronics7419
@proluxelectronics7419 5 лет назад
If it's ain't Broken, Bend it.....
@thehvachacker
@thehvachacker 5 лет назад
It was broke yet why did I have to bend it? How did it ever work with the gas aimed up and away from the hot surface ignitor?
@1keykneedeep
@1keykneedeep 5 лет назад
I would like to see that heat exchanger condition .Lmao
@thehvachacker
@thehvachacker 5 лет назад
It wasn’t bad or I would of poked holes through it instead of making it work
@phillipalv8641
@phillipalv8641 4 года назад
I had a problem with the igniter not lighting, would this be the igniter/ pilot assembly?
@oscarestrada5509
@oscarestrada5509 4 года назад
Check 120v coming out to ignator, if you do not get 120v then you have bad board
@glynwatkins9968
@glynwatkins9968 5 лет назад
he's lost the plot
@thehvachacker
@thehvachacker 5 лет назад
I hate losing the pilot
@erikcable1755
@erikcable1755 5 лет назад
200.00 repair,I would have sold a gas valve and board here...1200.00.cause i am a parts changer...
@thehvachacker
@thehvachacker 5 лет назад
They are already replacing a heat exchanger on another machine
@DONALD1951
@DONALD1951 5 лет назад
Never screw the customer!
@DONALD1951
@DONALD1951 5 лет назад
Gas valves rarely fail.
@rodgraff1782
@rodgraff1782 5 лет назад
Erik Cable. You would have looked pretty stupid charging for a gas valve and board, then getting the call to come back because you didn’t fix the problem. Anyone can speculate what is wrong,draw straws,and replace parts, but those who never learn how to troubleshoot and properly diagnose problems end up failing out of the trade at some point.
@jfrancis98
@jfrancis98 5 лет назад
It’s really really hard to watch a “technician” troubleshoot by randomly checking things. Then be praised for how great they are....am I being too harsh?
@JerryLynch2
@JerryLynch2 4 года назад
I am confused. He tracked it down by going through check points. He check limits, pressure switch first, made sure he was pushing 24 LV, then he checked power to gas valve, commented on inducer, is he suppose to start praying over it or something... perhaps a chanting session? He went upstream and started checking components that would affect the gas valve.
Далее
No Heat Service Call T-Stat Satisfied Upon Arrival
36:11
York RTU Multiple Problems
50:07
Просмотров 14 тыс.
Ajdarlar...😅 QVZ 2024
00:39
Просмотров 232 тыс.
When A Gang Leader Confronted Muhammad Ali
11:43
Просмотров 7 млн
ICP Gas Furnace not heating ignition problem easy fix
18:50
Top 5 Furnace Problems and How to Fix Them
20:11
Просмотров 1,4 млн
Locked Compressors
20:13
Просмотров 112 тыс.
Furnace Troubleshooting Step by Step with Multi Meter.
26:33